Introduction
The fan, pump and compressor motors are equipped with a thermal
protector that protects them against possible overheating.
2.1 Transport
The packed unit must remain:
a) Upright;
b) Protected against atmospheric agents;
c) Protected against impacts.
2.2 Handling
Use a fork-lift truck suitable for the weight to be lifted, avoiding any
type of impact.
2.3 Inspection
a) All the units are assembled, wired, charged with refrigerant and oil
and tested in the factory;
b) On receiving the machine check its condition: immediately notify
the transport company in case of any damage;
c) Unpack the unit as close as possible to the place of installation.
2.4 Storage
a) Keep the unit packed in a clean place protected from damp and
bad weather.
b) Do not stack the units;
c) Follow the instructions given on the package.
3
Installation
Y
For correct installation, follow the instructions given in par.7.2, 7.3
and 7.7.
!
The product installed must be suitably protected against fi re risk
(ref. EN378-3).
!
It is recommended that all chillers be fi tted with adequate pre-
fi ltration near the inlet water to the chiller.
!
Liquids to be chilled
The liquids to be chilled must be compatible with the materials used.
Examples of liquids used are water or mixtures of water and ethylene
or propylene glycols or oil.
The liquids to be chilled must not be fl ammable.
If the liquids to be chilled contain hazardous substances (e.g. ethylene/
propylene glycol), any liquid discharged from a leakage area must be
collected, because it is harmful to the environment. When draining
the hydraulic circuit, comply with the current regulations and do not
disperse the contents in the environment.
3.1 Operating space
Leave a space of 1.5 m around the unit.
Leave a space of at least 2 metres above the refrigerator in models with
vertical emission of condensation air.
ICEP002-005
3.2 Versions
Axial fans (A)
Do not create cooling air recirculation situations.
Do not obstruct the ventilation grilles.
The ducting of extracted air is not recommended for versions with axial
fans.
3.3 Water circuit
3.3.1
Checks and connection
Y
Before connecting the chiller and fi lling the circuit, check that all
the pipes are clean. If not, wash them out thoroughly.
Y
If the plumbing circuit is of the closed type (only for ICEP005),
under pressure it is advisable to install a safety valve set to: 6 bar.
Y
Always install mesh fi lters on the water inlet and outlet pipelines.
Y
If the hydraulic circuit is intercepted by automatic valves, protect
the pump with an anti-hammering system.
Y
If the hydraulic circuit is emptied for shut-down periods we recom-
mend that you add lubricating fl uid to the pump's impeller to avoid the
risk of blockage when it is re-started. In case the impeller is blocked
then you should unblock it manually.
Remove the rear cover of the pump and carefully turn the plastic fan.
If the impeller is stuck then remove the fan and turn the impeller shaft
directly. After un-blocking the impeller re-assemble the fan and cover.
Preliminary checks
1) Check that any shut-off valves in the idraulic circuit are open.
2) In the case of a closed water circuit, check that an expansion tank
of suitable capacity has been installed. See paragraph 3.3.3.
Connection
1) Connect the cooler to the inlet and outlet piping, using the special
connections located on the back of the unit.
We recommend the use of fl exible unions to reduce system rigidity.
2) Fill the water circuit using the fi tting provided on the rear of the
chiller (
).
3) The tank is equipped with a breather valve that should be operated
manually when fi lling the tank. Also, if the hydraulic circuit has high
points, install a vent valve at the highest points.
4) We recommend that taps are installed on the inlet and outlet pipes,
so that the unit can be excluded for maintenance when necessary.
5) If the chiller works with an open tank, the pump must be installed
on intake to the tank and on delivery to the chiller.
Subsequent checks
1) Check that the tank and the circuit are completely full of water and
that all the air has been expelled from the system.
2) The water circuit must always be kept full. For this reason, carry
out periodic checks and top the circuit up if necessary, or install an
automatic fi lling kit.
water characteristics
If not provided in the supply, fi t a mesh fi lter on the water inlet
Y,
water characteristics:
Temperature
≥50°F (10°C)
CL
ΔT IN/OUT
5-15°C
CaCO
Max % glycol
50
O
43.5-145 PSIg
Pressure
Fe
(3-10 barg)
PH
7.5-9
NO
Electrical
10-500 μS/cm
HCO
conductivity
Langelier
0-1
H
saturation index
SO
2-
<50 ppm
CO
4
NH
<1 ppm
Al
3
Please note that for special water types such as demineralized, deion-
ized or distilled it is necessary to contact the manufacturer to verify
which kind of chiller should be used since the standard material may
not be suitable.
3.3.2
Water and ethylene glycol
If installed outdoors or in an unheated indoor area, it is possible that
the water in the circuit may freeze if the system is not in operation dur-
ing the coldest times of the year.
To avoid this hazard:
a) Equip the chiller with suitable antifreeze protection devices, avail-
able from the manufacturer as optional accessories;
b) Drain the system via the drain valve if the chiller is to remain idle for
a prolonged period;
c) Add an appropriate quantity of antifreeze to the water in circulation
(see table).
Sometimes the temperature of the outlet water is so low as to require
the addition of ethylene glycol in the following percentages.
Outlet water
Ethylene glycol
temperature [°C]
(% vol.)
4
5
2
10
0
15
-2
20
-4
25
-6
30
3.3.3
Expansion tank (only for ICEP005)
To avoid the possibility of an increase or decrease in the volume of the
fl uid due to a signifi cant change in its temperature causing damage to
the machine or the water circuit, we recommend installing an expansion
tank of suitable capacity.
The expansion tank must be installed on intake to the pump on the rear
connection of the tank.
The minimum volume of an expansion tank to be installed on a closed
2 / 8
-
<50 ppm
70-150 ppm
3
<0.1 ppm
2
<0.2 ppm
<2 ppm
3
-
70-300 ppm
3
S
<0.05 ppm
2
<5 ppm
2
<0.2 ppm
Ambient
temperature
-2
-5
-7
-10
-12
-15