Troubleshooting
Problem
The display shows
"Error 24"
The display shows
"Error 25"
The display shows
"Error 30"
The display shows
"Error 35"
The display shows
"Error 40"
The display shows
„Error 41"
The display shows
„Error 42"
The display shows
„Error 43"
The display shows
„Error 60"
The display shows
„Error 61"
The display shows
„Error G1"
128
Cause
Pressure increase during
vacuum test.
Not sufficient pressure for
refrigerant pressure test.
Pressure drop during leak
test.
Residual pressure in the air
conditioning system.
Pressure drop during
pressure test.
Pressure drop during
pressure test.
Pressure drop during
pressure test.
The device was not able to
reduce the pressure suffi-
ciently to begin with the vac-
uum phase.
During the hybrid service
(flushing the service hoses
with hybrid oil), a vacuum
could not be achieved.
Pressure increase during the
hybrid service (flushing the
service hoses with hybrid oil).
A connection to the analysis
module could not be made.
VAS 581 001
Remedy
Check unit for leaks.
Check unit for leaks.
Check the refrigerant quan-
tity.
Is the ambient temperature
more than 10°C?
Check unit for leaks.
Drain and evacuate.
Check air conditioning
system and connections for
leaks.
Check air conditioning
system and connections for
leaks.
Check air conditioning
system and connections for
leaks.
Check air conditioning
system and connections for
leaks.
Check pressure transducer
calibration.
Are the service hoses
connected to the hybrid flush
container?
Is the hybrid flush container
fitted the right way round?
Check the connections for
leaks.
Are the service hoses
connected to the hybrid flush
container?
Is the hybrid flush container
fitted the right way round?
Are the service couplings
open?
Check the connections.
Are the LEDs on the module
activated?
EN