Access Power Solutions Installation Guide (APS6-3xx Series)
Prueba
Procedimiento de prueba
•
Set the Battery Test Interval to 0 days.
Battery Test
•
Set the Battery Test Duration to 30 minutes
•
Set the Battery Test Termination Voltage to a value approximately
2 volts below the float voltage.
•
Connect load to the system.
•
Start the Battery Test.
•
Ensure the SC200 indicates that a Battery Test has started.
•
Wait until the system voltage reduces below the Termination
Voltage.
•
Confirm the Battery Test fails.
•
Ensure the Battery Test Fail alarm is displayed on the SC200.
•
Ensure the Battery Test stops and the system voltage returns to
the float voltage setting.
•
Clear the Battery Test Fail alarm in DCTools/Web.
•
Set the Battery Test Duration to 1 minute.
•
Set the Battery Test Termination Voltage to a value approximately
10 volts below the float voltage.
•
Connect load to the system.
•
Start the Battery Test.
•
Ensure the SC200 indicates that a Battery Test has started.
•
Wait for the Battery Test Duration time to expire.
•
Confirm the Battery Test passes.
•
Ensure the Battery Test stops and the system voltage returns to
the float voltage setting.
•
Reset the Battery Test settings to the original values.