5.6
Connecting the switching output
(optional)
Comply with the pin layout
Further information:
"EIB 521x & EIB 5291S",
Page 311
Further information:
"EIB 528x", Page 314
Route the cable based on the mounting variant
Connect the cable to the respective connection
EIB 5212: X4; 4-pin M12 (male)
EIB 5282: X4; 4-pin M12 (male)
Basic insulation of the supply voltage is required.
The switching outputs are protected against wire
breakage (opener). The switching outputs have the
following switching behavior:
Message
Temperature
Warning
Setting: 100 °C < temp. < 130 °C
Resetting: temp. < 90 °C
OUT2
Alarm
Setting: temp. > 130 °C
Resetting: temp. < 120 °C
OUT1
HEIDENHAIN | EIB 5000 | Operating Instructions | 04/2021
5.7
Connecting functional ground
(EIB 52xx)
Route the functional ground based on the mounting
variant
Connect the functional ground to the respective
terminal with M5 thread
5.8
Connecting protective ground
(EIB 5181)
Route the protective ground based on the mounting
variant
Connect the protective ground to the respective
terminal with M5 thread
The cross section for connecting the
protective conductor should be at least
twice the cross section of the lines for the
temperature measurement; a minimum cross
section of 2.5 mm² is required, however.