Tripp-Lite SRCOOL3KTP Manual Del Propietário página 18

Ocultar thumbs Ver también para SRCOOL3KTP:
Idiomas disponibles

Idiomas disponibles

5. Operation
Setting
Temp Control Band
Upper Humid Control
Band
Low Temp Alarm Band
Maintenance Running
Time
Date and Time
Password
5.4 Maintenance Mode
From the home screen, click the Maintenance Mode on/off button. Maintenance Mode temporarily adjusts the cooling output
to 100% to help quickly exhaust heat from the rack to make it more comfortable when servicing IT equipment. No password is
required. The system returns to Auto Mode after 30 minutes. Disable Maintenance Mode in the control menu if the user wants
to prevent use of this feature.
Description
It is recommended to leave this at the default setting
of 5.4°F (3.0°C), except for low-load situations. If
the IT load is less than the cooler minimum capacity
or if the IT load changes often, set a higher band to
keep the rack temperature stable. A higher band can
help reduce the number of compressor on/off cycles.
For this, the recommended setting is 5.4° to 10°F
(3° to 6°C). If the IT load is greater than the AC unit's
minimum capacity or if the IT load is stable, consider
setting the band to its default or lower to optimize
temperature precision. Recommended setting: 3.6° to
5.4°F (2° to 3°C).
The allowable range above the humidity setting. For
example, a delta of 20% RH at a humidity setting
of 50% RH would mean the dehumidification cycle
would initiate when the humidity rises above 70% RH.
If the discharge temperature falls below this value, an
alarm is triggered.
Maintenance Mode duration. If the user does not turn
off Maintenance Mode from the home screen, the AC
unit will automatically revert to normal operation after
this time.
Date: yyyy/mm/dd
Time: 24-hour hh/mm/ss
Allows user to change password.
Notes
If setting Control Mode to Return Air, you
MUST ADJUST this setting to be based off
of the return air temperature instead.
18
loading