CAUTION
While connecting the wires, please strictly follow the wiring diagram.
•
The refrigerant circuit can become very hot. Keep the interconnection cable away from the
•
copper tube.
5. Clamp down the cable with the cable clamp.The cable must not be loose or pull on the u-lugs.
6. Reattach the electric box cover.
Power Specifications
NOTE: Electric auxiliary heating type circuit breaker/fuse need to add more than 10 A.
MODEL(Btu/h)
POWER
CIRCUIT BREAKER/
FUSE(A)
MODEL(Btu/h)
POWER
CIRCUIT BREAKER/FUSE(A)
MODEL(Btu/h)
POWER
CIRCUIT BREAKER/
FUSE(A)
MODEL(Btu/h)
POWER
CIRCUIT BREAKER/FUSE(A)
Page 38
Indoor Power Supply Specifications
≤18K
PHASE
1 Phase
208-240V 208-240V 208-240V 208-240V 208-240V
VOLT
25/20
≤36K
PHASE
3 Phase
380-420V
VOLT
25/20
Outdoor Power Supply Specifications
≤18K
PHASE
1 Phase
208-240V 208-240V 208-240V 208-240V 208-240V
VOLT
25/20
≤36K
PHASE
3 Phase
380-420V
VOLT
25/20
19K~24K 25K~36K 37K~48K 49K~60K
1 Phase
1 Phase
32/25
50/40
37K~60K
3 Phase
3 Phase
380-420V
208-240V
32/25
32/25
19K~24K 25K~36K 37K~48K 49K~60K
1 Phase
1 Phase
32/25
50/40
37K~60K
3 Phase
3 Phase
380-420V
208-240V
32/25
32/25
1 Phase
1 Phase
70/55
70/60
≤36K
37K~60K
3 Phase
208-240V
45/35
1 Phase
1 Phase
70/55
70/60
≤36K
37K~60K
3 Phase
208-240V
45/35