Step 2:
Hang indoor unit
1. Use the included paper template to cut a rectangular hole in the ceiling, leaving at least 1m (39")
on all sides. The cut hole size should be 4cm(1.6") larger than the boby size.
Be sure to mark the areas where ceiling hook holes will be drilled.
(A)
Refrigerant piping side Drain hose side
780mm / 30" (Suspension bolt)
840mm / 33"(Body)
880mm / 34.7"(Ceiling opening)
950mm / 37.4"(Panel)
24-48K Classic Models, size of the hole on the false ceiling
Drain hose side
Refrigerant piping side
545mm / 21.5" (Suspension bolt)
570mm / 22.4"(Body)
600mm / 23.6"(Ceiling opening)
647mm / 25.5"(Panel)
12-24K Compact Models, size of the hole on the false ceiling
>100cm / 39"
>100cm / 39"
>100cm / 39"
>100cm / 39"
Page 23