DA
Book_81307110_CA44x.indb 106
Book_81307110_CA44x.indb 106
If the sensor is loop powered:
5
4
3
2
1
V+
H
Shld
L
V-
CA 442
If additional temperature module, CA 442 ID 5 and CA 442 ID 6 are used.
Tabel 8b. Configuration of the temperature input on CA 442 ID 5
#
Signal
Dir.
6
←
Sensor 1
←
7
GND
←
8
Sensor 2
9
←
GND
10
←
Sensor 3
←
11
GND
←
12
Sensor 4
←
13
GND
14
←
0 V
←
15
Analogue mA in
Tabel 8c. Configuration of the temperature input on CA 442 ID 6
#
Signal
Dir.
6
←
Sensor 1
←
7
GND
8
←
Sensor 2
9
←
GND
10
←
Sensor 3
←
11
GND
←
12
Sensor 4
←
13
GND
14
←
0 V
←
15
Analogue mA in
+
-
0V mA
in
14
15
Description
Temp. sensor 1: T1 Stator L2, Pump 1
Temp. sensor 2: T2 Stator L3, Pump 1
Temp. sensor 3: T1 Stator L2, Pump 2
Temp. sensor 4: T2 Stator L3, Pump 2
N/A in CA 442 ID 5
Description
Temp. sensor 1: T1 Stator L2, Pump 3
Temp. sensor 2: T2 Stator L3, Pump 3
Temp. sensor 3: T1 Stator L2, Pump 4
Temp. sensor 4: T2 Stator L3, Pump 4
N/A in CA 442 ID 6
106
Vibration
sensor
05/04/2022 12:18:53
05/04/2022 12:18:53