4.4
Characteristics of construction
Dimension
H 200 x W 92 x D 50mm
Weight
700g (with batteries)
Measurement
400ms
acquisition
Bargraph
35 segments, refresh rate 30ms
4.5
Power supply
Power supply
6 x 1.5V MA batteries
Automatic switching-
10 minutes of non-use
off time
4.6
Compliance with international standards
Electric safety
Application of safety rules as per standard
CEI-61010-1-Ed.2:2001.
600V CAT-IV. Pollution level 2. Double
insulation.
Electromagnetic
Compliant with standard EN-61326:2006
compatibility
Residential environment
Electric safety in LV
In the insulation and Ohm/Continuity
distribution networks
functions, the entire measurement range
complies with uncertainties requirements
of standards IEC-61557-1/-2/-4:2007 and
IEC-61557-10:2000
Mechanical strength
Free fall: 1m (tested in accordance with
standard IEC-68-2-32)
Level of protection of
IP51 according to EN-60529
the housing
5. MAINTENANCE
For maintenance, use only the spare parts specified.
5.1
Cleaning
Disconnect the unit completely and turn the rotary switch to
Use a soft cloth, dampened with soapy water. Rinse with a damp
cloth.
Dry rapidly with a dry cloth or forced air. Do not use alcohol,
solvents, or hydrocarbons.
33
.