7 - WATER CONNECTIONS
7.1 - Connection to be tightened (HELIOTHERME
The side of the HELIOTHERME
turning it (for HEATING applications). Ensure that the cable glands on the motor terminal box are facing downwards to ensure the
assembly is correctly sealed.
The hydraulic connection on the HELIOTHERME
and the general supply pipes must be connected and tightened according to good working practice, namely, using two adjustable
wrenches to avoid any torsion of the coil collector.
CIAT shall in no way be held liable for damage to the coil if these installation instructions are not followed and the warranty shall
be invalidated.
Two keys are used to ensure the counter
torque; the HELIO connection tube will not be
pierced.
7.2 - Connection to be welded (HELIOTHERME
Ensure that the casing and the rubber caps are protected from the excessive heat produced during welding by using a damp cloth
when welding between the HELIOTHERME
Welding must be carried out according to good working practice, especially on the filler metal.
7.3 - Condensate drain connection (HELIOTHERME
For COOLING applications, the condensate drain pan is integrated into the HELIOTHERME
to its diamond pointed based.
2nd gasket
1st gasket
M5 CBLX screw
Procedure for fitting the union on the pan:
1. Position the 1st gasket into the lower groove on the union
2. Position the 2nd gasket into the upper groove on the union
3. Fix the assembly onto the condensate drain pan using the M5
CBLX screw supplied in the threaded insert fixed onto the pan.
H4000 HELIOTHERME
®
hydraulic connection may also be positioned to the left or right of the air flow direction simply by
®
LP water version is screwed in using threaded unions. The coil supply pipes
®
and the supply pipes.
®
Upper groove
Lower groove
LP Water)
®
If only one key is used, the connection tube may
twist and be pierced.
This is not covered by the CIAT warranty
HP fluid)
®
used for cooling or reversible purposes)
®
Condensate
drain pipe
Condensate drain pan connection
Once the union is fitted with these gaskets, fit the pipe onto the
union (outer diameter 32 mm). The gaskets provide an adequate
seal for the union.
Nevertheless, it is important to ensure that this connection
between the union and the pipe does not bear all the weight of
the drain column fitted with a siphon which must be installed
according to good working practice (risk of detachment).
EN-30