In the case of substantial deviations from
the national technical approvals, e.g. with
the use of non-original filters, the utilisation
of the constructed product / the Ultrasep is
not proven by the authority.
In such cases an agreement with the
responsible local authority will be required
for each individual case.
Shut the condensate supply off.
Take the sedimentation insert (N) carefully
out.
Remove the coalescence filter (E) and
press the foam body out and clean with
clear warm wate.
Clean insert (N). Press the coalescence filter
(E) back in. Reinsert the insert with the filter.

Technical data

Screw compressor
DS
Mineral oil
0070
71
0145
147
0265
147-282
0530
282-565
1060
565-1131
2120
1131-2262
4240
2262-4523
Installable compression power in cfm.
Temperature ranges
Standard:
with heater:
Synthetic oil
71
147
106-212
212-424
424-848
848-1696
1696-3392
+34 °F to + 140°F
-13 °F to + 140°F
Troubleshooting
Fault
Water in oil canister.
Cause
- Excessive fluctuation in condensate supply.
Remedy
- Raise oil overflow.
Fault
Float comes up.
Cause
- Clogging of scavengers by emulsion.
Remedy
- Check the adsorber and replace it, if necces-
sary. Retrofitting of a heater is recommend-
ed.
Fault
Clotting of oil at the surface.
Cause
- Bacterial invasion.
Remedy
- Clean, disinfect the container. Replace all
PUR foams and scavengers.
Protection of the environ-
ment
Oil and oil containing wastes can cause
environmental damage and must therefore
disposed of properly by specialised compa-
nies. Addresses can be found in the branch
directory or you can enquire at your local
authorities about proper waste disposal pro-
cedures.