AC connection
An AC bayonet connector on the underside of the
unit is used for the three-wire grid connection (L, N,
PE) of the Solar Inverter. The grid connection should
always be 1-phase. Feeding is single-phase via AC
terminal 2.
If several Solar Inverters are operated in parallel in
a 3-phase grid, AC terminal 2 of the unit must be
distributed uniformly among the grid phases L1, L2
and L3 to avoid unequal loading.
Three-phase grid connection
L1
L2
L3
N
PE
2
1
2
3
4
3
Solar Inverter 1 Solar Inverter 2 Solar Inverter 3
Single-phase grid connection
L1
N
PE
2
1
2
4
3
Solar Inverter 1 Solar Inverter 2 Solar Inverter 3
AC bayonet connector assembly
The AC bayonet connector is approved for cable
sheath diameters between 13 mm and 20 mm.
1 Strip the voltage-free line and the cable ends.
52,5 (PE 55)
10
1
2
1
4
3
4
1
2
1
4
4
3
3
For cables with a sheath diameter between 16 and
20 mm adapt the cable gland accordingly. To do this,
cut out the inner section of the blue sealing ring.
2 Slide the cable gland and the plug housing onto
the cable.
3 Connect the cable ends to the plug terminals in
accordance with the pin assignment.
Tightening torque: 0.7 Nm.
CAUTION
Incorrect pin assignment may result in destruction of
the unit!
Pin assignment for AC bayonet connector
The diagram shows the connections inside the AC
connector, as indicated by the cut-out at the PE
connection.
3
4
1 = N
2 = L (feed-in phase)
3 = not used
4 = not used
= PE (protective earth conductor)