12 FINAL CHECKS AND TEST RUN

The installer is obliged to verify correct operation of unit
after installation.

12.1 Final checks

Before switching on the unit, read following recommendations:
When the installation and parameter setting are
completed, cover all the sheet metal of the unit well.
The unit should be maintained by professionals.

12.2 Test run operation(manually)

TEST RUN is used to check correct operation of the
valves, air purge, circulation pump operation, cooling,
heating and domestic water heating.
Go to
> FOR SERVICEMAN> 11.TEST RUN.
Press
. The password is 234. The following page will
be displayed:
11 TEST RUN
ACTIVE THE SETTINGS AND
ACTIVE THE "TEST RUN"?
NO
CONFIRM
If YES is selected, the following pages will be displayed:
11 TEST RUN
11.1 POINT CHECK
11.2 AIR PURGE
11.3 CIRCULATED PUMP RUNNING
11.4 COOL MODE RUNNING
11.5 HEAT MODE RUNNING
ENTER
11 TEST RUN
11.6 DHW MODE RUNNING
ENTER
If POINT CHECK is selected, the following pages will be
displayed:
11 TEST RUN
SV2
SV3
PUMPI
PUMPO
PUMPC
ON/OFF
11 TEST RUN
IBH
AHS
SV1
PUMPD
PUMPS
ON/OFF
YES
PUMPI will run according to the output and running time that
has been set.
When CIRCULATED PUMP RUNNING is selected, the
following page will be displayed:
1/3
OFF
OFF
OFF
OFF
OFF
2/3
OFF
OFF
OFF
OFF
OFF
52
11 TEST RUN
TBH
ON/OFF
Press ▼ ▲ to scroll to the components you want to check
and press
.
CAUTION
Before using POINT CHECK, make sure that the
water system and the tank are filled with water,
and air is expelled, otherwise the pump or
backup heater (optional) may be broken.
If you select AIR PURGE, the following page will be
displayed :
11 TEST RUN(POINT CHECK)
AIR PURGE PUMPI OUTPUT
AIR PURGE RUNNING TIME
ENTER
CONFIRM
11 TEST RUN
TEST RUN IS ON.
CIRCULATED PUMP IS ON.
CONFIRM
When circulation pump running is turned on, all running
components will stop. 60 seconds later, the SV1 will be off,
the SV2 will be on, 60 seconds later PUMPI will operate. 30s
later, if the flow switch checked normal flow, PUMPI will
operate for 3min, after the pump stops 60 seconds, the SV1
will close and the SV2 will be off. 60s later the both PUMPI
and PUMPO will operate, 2 mins later, the flow switch will
check the water flow. If the flow switch closes for 15s, PUMPI
and PUMPO will operate until the next command is received.
When the COOL MODE RUNNING is selected, the following
page will be displayed:
3/3
OFF
70%
20min
EXIT