Function indicator
Indicates modes of operation
MAN = OFF (Automatic control)
MAN = ON (Manual control)
AUX = ON (program in reset)
PRG = ON (program running)
"Raise" and "Lower" key
Press to increment (decrement) any numerical
parameter •• Increment (decrement) speed is
proportional to time key stays pressed •• The operation
is not cyclic: once the maximum (minimum) value of a
field is reached, the value will not change even if the
key remains pressed.
M/A key
Function defined with butt parameter
• Power Supply
Standard:
100...240Vac/dc ±10%
~
12
Optional:
PWR
20...27Vac/dc ±10%
~
13
50/60Hz
• Outputs
User configurable
(-) NC
14
generic outputs
- 5A/250Vac relay, cosϕ=1
C
15
- 11Vdc logic, Rout=220Ω
(6V/20mA)
(+) NO
16
(-) NC
17
C
18
(+) NO
19
(-) NC
20
C
21
(+) NO
22
• Serial line
Configurable serial
27
-
line isolated to 1500V
Tx
Passive current loop
26
+
(max. 1200 baud)
25
-
RS422/485 or RS232
Rx
(optional)
24
+
• Linear (V)
Linear input in
2
dc voltage
0...50mV, 10...50mV,
0...10V, 2...10V
1
3 • DESCRIPTION OF FACEPLATE
4 • CONNECTIONS
!
12
13
14
15
16
17
18
19
20
21
22
A (Data +)
B (Data -)
Tx
1800
GND
Rx
RS485 2-wires
RS232
• Linear (I)
Linear input in
-
dc current
0...20mA, 4...20mA
+
User configurable
33
+W2
generic output
analogue output isolated
32
+W1
to 1500V
(0 ... 10V, 0 ... 20mA,
4 ... 20mA)
31
0V
33
11
32
10
31
9
30
8
29
7
28
6
27
5
26
4
25
3
24
2
1
1600
• Pt100 2-wires or PTC
Use wires of adequate
4
diameter (min. 1mm
PT100, JPT100, PTC
2
-
1
+
19
Indication of output states
OUT 1 (Main); OUT 2 (AL 1);
OUT 3 (AL 2); OUT 4 (HB)
PV Display: Indication of process variable
Error Indication: LO, HI, Sbr, Err
LO = the value of process variable is < di LO_S
HI = the value of process variable is > di HI_S
Sbr = faulty sensor or input values
higher than max. limits
Err = PT100 third wire opened for PT100, PTC or
input values lower than min. limits
(i.e.: TC wrong connection)
SV display: Indication of setpoint
Bargraph: Percentage display for variable defined
with bArG parameter
Function key
Gives access to the various configuration phases
•• Confirms change of set parameters and browses
next or previous parameter (if Auto/Man key is
pressed)
Key " ":
Function defined with but. 2 parameter
• Outputs
User configurable
generic output
- 5A/250Vac relay, cosϕ=1
- 11Vdc logic,
Rout=220Ω (6V/20mA)
• Transmitter supply
Transmitter supply isolated
1500V
10/24Vdc, max. 30mA
short-circuit protection
• Digital inputs
Digital inputs isolated
1500V
- NPN 24V, 4,5mA
- PNP 24V, 3,6mA
(12V, 1,2mA)
• Auxiliary input
Auxiliary input isolated
1500V
Current transformer
50mAac; 1,5Ω; 50/60Hz
Remote setpoint
0...20mA, 4...20mA, 5Ω,
0...1V, 0...10V,> 1MΩ
• Inputs
Available thermocouples:
J, K, R, S, T, B, E, N,
Ni-Ni18Mo, L NiCr-CuNi
- Observe polarities
- For extensions, use the
correct compensating
cable for the type of TC
used
3
2
)
2
T
1
11
-
Out4
(AL3/HB)
10
+
+ Vt
9
5
GND
8
IN2
7
IN1
5
COM
~
6
+
~
-
5
• TC
-
2
1
+
• Pt100 3-wires
3
2
T
1