gefran 1600P Manual De Uso página 18

Programador / regulador
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 66
1 • INSTALLATION
• Dimensions and cut-out; panel mounting
48
108 96
92
113
10
96
108 96
92
113
10
Panel mounting:
To fix the unit, insert the brackets provided into the seats on either side of the case. To
mount two or more units side by side, respect the cut-out dimensions shown in the
drawing. To obtain IP65 faceplate protection level, remove the device from the box,
apply the gasket (supplied) with adhesive to the front edge of the box, and then reinsert
the device.
CE MARKING: EMC conformity (electromagnetic compatibility) with EEC Directive
89/336/CEE with reference to the generic Standard EN61000-6-2 (immunity in
industrial environments) and EN50081-1 (emission in residential environments).
BT (low voltage) conformity respecting the Directive 73/23/CEE modified by the
Directive 93/68. Limitations: model 1800P conforms to Standard EN55011 for
emissions radiated in industrial environment.
MAINTENANCE: Repairs must be done only by trained and specialized personnel. Cut
power to the device before accessing internal parts.
Do not clean the case with hydrocarbon-based solvents (Petrol, Trichlorethylene, etc.).
Use of these solvents can reduce the mechanical reliability of the device. Use a cloth
dampened in ethyl alcohol or water to clean the external plastic case.
SERVICE: GEFRAN has a service department. The warranty excludes defects caused
by any use not conforming to these instructions.
1600P / 1800P
CONTROLLER / PROGRAMMER
70
115
44,5
115
115
92
!
For correct and safe
installation, follow the
instructions and observe
the warnings contained
in this manual.
USER'S MANUAL
SOFTWARE VERSION 3.2x
code 80090A / Edition 08 - 06/03
TECHNICAL SPECIFICATIONS
2 •
Display
Keys
Accuracy
Main input
Thermocouples
Cold junction error
RTD type (scale configurable within indicated
range, with or without decimal point)
PTC type (on request)
Max line resistance for RTD
Safety
°C / °F selection
Linear scale ranges
Controls
pb / dt / di
Action
Control outputs
Cycle time
Main output type
Softstart
Maximum power limit heat / cool
Fault power setting
Automatic blanking
Configurable alarms
Alarm masking
Type of relay contact
Logic output for static relays
Remote setpoint or
ammeter input (options)
CT scale range
Transmitter power supply (optional)
Analogue retransmission
signal (optional)
Logic inputs (optional)
Serial interface (optional)
Baud rate
Protocol
Power supply (switching type)
Faceplate protection
Working / Storage temperature range
Relative humidity
Installation
Weight
EMC conformity has been tested with the following connections
FUNCTION
Power supply cable
Relay output cable
Digital communication wires
C.T. connection cable
TC input
Pt100 input
18
2 x 4 digits, green, height 10 and 7mm (1600P), 20 and 30 mm (1800P)
5 mechanical keys ( , Man/Auto, INC, DEC, F)
0.2% full scale at 25°C room temperature
TC, RTD (Pt100 - JPT100), PTC,
60mV Ri ≥ 1MΩ; 10V Ri ≥ 10KΩ; 20mA, Ri = 50Ω
IEC 584-1
(J, K, R, S, T, B, E, N, Ni-Ni18Mo, L NiCr-CuNi)
0,1° / °C
DIN 43760 (Pt100, JPT100)
990Ω, 25°C
20Ω
detection of short-circuit or opening of probes,
LBA alarm, HB alarm
configurable from faceplate
-1999 to 9999 with configurable decimal point position
PID, Self-tuning, on-off
0.0 ... 999.9% / 0.00 ... 99.99min / 0.00 ... 99.99min
Heat / Cool
on / off, pwm
0.1 ... 200 sec
Relay, Logic, Continuous (optional)
0.0 ... 500.0 min
0.0 ... 100.0 %
-100.0 ... 100.0 %
Optional exclusion, displays PV value
3 configurable alarms type: max, min, symmetrical,
absolute or relative, LBA, HB
- exclusion during warm up
- latching reset from faceplate or external contact
NO (NC), 5A, 250V, cosϕ = 1
11Vdc, Rout = 220Ω (6V/20mA)
0 ... 10V, 2 ... 10V, Ri ≥ 1MΩ
0 ... 20mA, 4 ... 20mA, Ri = 5Ω
Potentiometer > 500Ω,
TA 50mAac, 50/60Hz, Ri = 1,5Ω,
isolation 1500V
configurable 0, ... , 100.0A
filtered 10 / 24Vdc, max 30mA
short-circuit protection, isolation 1500V
10V / 20mA, isolation 1500V
24V NPN, 4.5mA; 24V PNP, 3.6mA
isolation 1500V
CL; RS422/485; RS232; isolation 1500V
1200 ... 19200
GEFRAN / MODBUS
(std) 100 ... 240Vac/dc ±10%; 50/60Hz, 18VA max
(opz.) 20...27Vac/dc ±10%; 50/60Hz, 11VA max
IP65
0...50°C / -20...70°C
20 ... 85% non-condensing
Panel, plug-in from front
400g (1600P); 600g (1800P) complete version
CABLE TYPE
LENGTH
1 mm
2
1 m
1 mm
2
3,5 m
0,35 mm
2
3,5 m
1,5 mm
2
3,5 m
0,8 mm
2
compensated
5 m
1 mm
2
3 m
Tabla de contenido
loading

Este manual también es adecuado para:

1800p

Tabla de contenido