5 LCS-Tool
5.2 Operation
Figure 18: Recommissioning / Save (A) and Load (B)
5.2.1 Recommissioning
After commissioning is completed by entering the SMA Grid
Guard codes, it is possible to restart operation of the
Inverter Manager.
Procedure:
INFORMATION
Pressing the [recommissioning] button
automatically logs out the user who is currently
logged in.
Procedure:
1. Open the LCS-Tool.
2. Log in as an Installer.
3. Open the Setup > General menu.
4. Select the [recommissioning] button.
28
IMVIOBOX-IA-xx-19
5.2.2 Saving and Loading a
Configuration File
After commissioning is completed by entering the SMA Grid
Guard codes, it is possible to save the configuration of the
Inverter Manager in a configuration file. This configuration
file can be loaded again at a later time. Loading the
configuration file restores the configuration state of the
Inverter Manager after commissioning.
Procedure:
1. Open the LCS-Tool.
2. Log in as an Installer.
3. Open the Setup > General menu.
4. To save the configuration of the Inverter Manager,
select the button (A).
5. To load the configuration of the Inverter Manager,
select the button (B).