Grundfos CIM 500 Instrucciones De Instalación Y Funcionamiento página 36

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Object
Description
Custom device
If ticked, CIM 500 is configured to use a BACnet custom device instance number.
instance enable
Foreign Device
If ticked, CIM 500 is configured as a foreign device.
IP Address
Enter the foreign IP address.
UDP Port
Enter the foreign UDP port number. The default number is 47808.
Enter the time period in seconds during which the foreign device must re-register on the
Re-Register Time
BACnet network.
If enabled and BACnet communication stops, the watchdog timer restarts the internal network
module if it times out.
Network Watchdog
Timer
You can configure the time-out from 2 minutes to 1440 minutes in steps of 1 minute.
A value of 1 is illegal and a value of 0 disables the watchdog.
288
Tabla de contenido
loading

Tabla de contenido