Shutting Down The Chiller; Switching On/Off In Daily Operation - omi CHW Serie Manual De Uso Y Mantenimiento

Chiller a líquidos
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

710.1760.00.01-03A
To access the "Pr1" user level:
1. Press the
+
play shows the first parameters with "PAS".
2. Press the
key to confirm and use the arrow keys
"1". Press the
3. Select the parameter you require.
4. Press the
key to change its value.
5. Change the value with the
6. Press the
key again to confirm the new value. After a few seconds, the next parameter ap-
pears.
7. To exit the program: Press the
sec. (timeout), without pressing any key.
List of parameters that can be changed with the procedure described:
Code
Meaning
ST01
Set-point
ST02
Differential
(*probe set-point at inlet)
6.5

SHUTTING DOWN THE CHILLER

SWITCHING ON/OFF IN DAILY OPERATION

MODEL: CHW 09
1)
Move the main switch to position "0". The system then switches off immediately.
MODEL: CHW 11 – CHW 36; CHG 08 (Controller Type "A", see 6.4)
Via stand-by mode:
1) Stop the compressor by keeping the
Move the main switch of the chiller to position "0".
2)
Via the main switch:
Move the main switch to position "0". The system then switches off immediately. This procedure
should only be used in an emergency.
MODEL: CHW 29 – CHW 602; CHO 29 – CHO 149; CHG 24 – CHG 140 (Controller Type "B", see 6.4)
Via stand-by mode:
Stop the system by keeping the
1)
to switch off. The chiller is fitted with a turn-off delay to protect the components. The system
does not switch off immediately.
2) Move the main switch of the chiller to position "0".
Via the main switch:
Move the main switch to position "0". The system switches off immediately. This procedure should
only be used in an emergency.
MODEL: CHW 682 – CHW 3652; CHG 180 – CHG 365 (Controller Type "C", see 6.4)
Via stand-by mode:
Stop the system by pressing the
1)
switched off. The chiller is fitted with a turn-off delay to protect the components. The system does
not switch off immediately.
2) Move the main switch of the chiller to position "0".
Via the main switch:
Move the main switch to position "0". The system switches off immediately. This procedure should
only be used in an emergency.
Caution: Turn the main switch off. All the safety devices set by the electronic controller as well
as the antifreeze heating and compressor heating are switched off!
keys for a few seconds (the
key to confirm.
and
keys.
+
button depressed (for 10 seconds).
key depressed for 3 seconds and waiting for the compressor
key (LED goes out) and waiting until the compressor has
and
LEDs start to flash), the upper dis-
and
keys when a parameter name is displayed or wait 15
CHW
CHW*
with tank
without tank
15°C
20°C
3°K
3°K
25
14/11/2012
in order to enter the password
CHG
CHG*
with tank
without tank
-10
-5
3
3