applicable provisions and the anchor manufacturer's
published installation instructions.
The concrete slab/pad must meet the requirements (Figure
6) and the generator must be anchored with the anchors of
Anchor Types 1 or 2.
There are three 7/16" hole locations (A, Figure 6) in the base
of the generator in which to anchor the unit.
Anchor Types:
1.
Qty (3) 3/8" SS ITW RED HEAD LDT, Anchor embedded
2 ½" (64mm) in 3000 psi concrete. 3" (76mm) from the
edge minimum, 6" (152mm) spacing minimum.
2.
Qty (3) 3/8" SS Powers/Dewalt Power Stud +SD2 Anchor
embedded 2 ½" (64mm) in 3000 psi concrete. 3" (76mm)
from the edge minimum, 6" (152.4mm) spacing minimum.
There are four 7/16" hole locations (A) in the base of the
generator in which to anchor the unit.
6
Concrete Slab/Pad Type
WIND
PAD
PAD DIMENSIONS
RATING
MODEL
MPH
Width
Up to 140
Pre-
29in
cast Pad
(737mm)
(contact
dealer)
140 to 175 Pre-
29in
cast Pad
(737mm)
(contact
dealer)
140 to 175 Poured
30in
(762mm)
These items are available at your local service dealer.
14
CONCRETE
SPEC
Length
Thickness
32in
3in
3000 PSI
(813mm)
(76mm)
32in
4in
3000 PSI
(813mm)
(102mm)
32in
5in
3000 PSI
(813mm)
(127mm)
 NOTICE: Unless mandated by local or state codes, or
required to achieve wind rating, a concrete slab/pad is not
required
Panel Attachment in Wind Rated Areas
To achieve a wind rating of 140 mph and above, (2) 1/4-20
Screws (B, Figure 7) are included and must be installed in the
bottom of the front panel
7

Electrical and Fuel Inlet Locations

The 3/4 inch N.P.T. fuel inlet connector (A, Figure 8) and
electrical inlet locations (B) are shown below.
A ½ inch knock-out is provided for the electrical inlet. This
inlet may be enlarged or supplemented to accommodate a
maximum conduit size of 1-½ inches. Make sure that the
installed conduit(s) enter the unit in zone (C) as shown in the
drawing below so that they properly enter the electrical box
and do not interfere with the fully opened roof.