For power output connection (L1, L2, Neutral (N), and Ground), refer to the National Electric Code (NEC) and local
codes.
•
For communication wires use 600V wire and #18 AWG [1mm
500 ft (150 m).
•
When connecting to the terminal block, fasten only one wire to each connector screw.
•
Torque terminal block screws to 4.4 in-lb [0.5 Newton meter (N·m)].
•
Torque circuit breaker connections to 45 in-lb (5 N·m).
AC System Connections
A single-phase, three-wire AC connection system is used in
the generator (Figure 17) The stator assembly consists of a
pair of stationary windings with two leads brought out of each
winding. The junction of leads 22 and 33 forms the neutral
lead, as shown schematically and as a wiring diagram.
NOTICE: Neutral is not bonded to ground at generator.
NOTICE: Generator must be used with only an UL listed
transfer switch that is compatible with the generator.
Wire Type
Connect To
2
18AWG[1mm
] conductors,
Refer to the Amplify Gateway
600V minimum, 90°C Cu wire.
Manual
2
18AWG[1mm
] conductors,
600V minimum, 90°C Cu wire.
2
18AWG[1mm
] conductors,
600V minimum, 90°C Cu wire.
2
18AWG[1mm
] conductors,
600V minimum, 90°C Cu wire.
2
18AWG[1mm
] conductors,
Not used
600V minimum, 90°C Cu wire.
2
18AWG[1mm
] conductors,
600V minimum, 90°C Cu wire.
2
18AWG[1mm
] conductors,
600V minimum, 90°C Cu wire.
2
18AWG[1mm
] conductors,
600V minimum, 90°C Cu wire.
2
14AWG [2.5mm
] 600V
Transfer switch Utility
minimum, 90°C Cu Wire.
2
14AWG [2.5mm
] 600V
Transfer switch Utility
minimum, 90°C Cu Wire.
2
] twisted-pair conductors that do not exceed a length of
Notes
Comm to WIFI module.
Twisted pair #1: +12V and
GND.
Twisted pair #2: (A) and (B).
Not used
Voltage Sensing for GENSET
Start. Use either this signal
or two-wire Start Signal for
GENSET Start Signal (still
required in two-wire start
configuration for battery
charger).