Unit Installation – SBH Units
G Check the dimensions of the unit illustrated in the following figure:
Electrical box
(PCB, Transformer and MF Capacitor)
Air
flow
Filter
Shelter board
Optional Air Flow (Lower air inlet)
Shelter board
Filter
Air flow
Connection of Ducting
Air outlet
duct (local
Shelter board
procurement)
(factory fitted)
G
The filter is factory fitted to the rear of the unit as
shown above.
G
If lower air inlet is required, remove the filter and 6
screws from the shelter board, reposition shelter board
on to the rear of the unit and replace the filter.
Ensure design of the air inlet duct work allows access
!
to replace or clean the filter.
The maximum static pressure of the Air Outlet duct
!
should not exceed 30Pa/3mmAq.
Installing Ø 10 Hanging Bolts (4 pieces)
G
Install the hanging bolts at the intervals shown in the
above figure.
G
Use Ø 10 hanging bolts (to be locally procured).
How to Install the Hanging Bolts
Installation on a newly installed concrete slab:
Use insert brackets or foundation bolts for the installation.
Knife-shaped
Sliding
bracket
bracket
(Foundation bolt for
hanging the piping)
Tel: 01823 665660
All manuals and user guides at all-guides.com
I
U
L
NDOOR
NIT
OCATION
Air outlet
Hanging bolt pitch
Unit dimension
Installation on an existing concrete slab:
Air inlet duct
Use hole-in anchors, hole-in plugs
(local procurement)
or hole-in bolts for the installation.
Installation on a steel frame:
Use the angular
bracket in the
structure or install
one for support.
Installation on a wooden structure:
Place a length of wood of the appropriate size across two
beams and install the hanging bolts into this length of wood.
Hanging Unit
(1) Raise the unit by using a lift-
(2) Install the unit horizontally
Reinforcing
bar
Foundation
bolt
~ 17 ~
www.heronhill.co.uk
Refrigerant pipe
connection
(Liquid ø6.4)
Refrigerant pipe
connection
(Gas ø12.7)
Drain pipe connection
(1" BSP threaded
connection)
Air inlet
Washable filter
Hanger bolt
Hanging
bolt
Cross
length
of wood
Hanging
bolt
ing device, then secure the
hangers to the hanging
bolts. Be sure to fix the nuts
onto both the upper and
Washer
under side of the hanger
Hanging
and the washer (under side
Bolt
only);
by using a level. Failure to
do this will cause water
leakages.
Fax: 01823 665807
Terminal box
wiring connections
GB
Angular bracket
for support
Beam
Ceiling
Nut
Hanger