Additional device-specific information
On delivery the device is not operational !
The IO-Link process data contains the following values
•
The level value is NoData (0x7FFC, 32764 dec).
•
The Device Status is Functional Check (3)
•
Both SSCs are 0
Event Parameter missing (0x6321, 25377 dec) is pending
Set the device into operational state
Adjust parameter Reference height
Depending on the tank height, the parameter Reference height has to be considered. It has to be
changed from 'Initial value' to the height of the applied tank.
Adjust dependent parameters to Reference height
•
Switch point parameters SSC1-Param.SP1, SSC2-Param.SP1 are initially set to the smallest
expected Reference height.
•
Analog end point Parameter AEP2 is also initially set to the smallest expected Reference height.
Please readjust those parameters according your expected Reference height
25/25