Refrigerant piping system
Prohibited pattern
1
48k
• Capacity sum of indoor units is over 160kBtu/hr.
Pattern
1
Indoor unit
Low pressure Gas pipe
Outdoor
High pressure Gas pipe
Unit
1) Keep the 40m distance from the first branch to the farthest indoor.
2) Keep the horizontal level between HR units.( for example, the same flour. )
Y branch
36
Outside Unit
All manuals and user guides at all-guides.com
HR1
2
3
4
48k
48k
48k
1
12k
Y Branch pipe
A
HR
Unit
Liquid pipe
Indoor
Indoor
Unit
Keep the sum of indoor capacity is under 160kBtu/hr
1) under 40m
2) Same horizontal level
Indoor
Indoor
Indoor
Indoor
Unit
Unit
Unit
Unit
Keep the sum of indoor capacity is under 160kBtu/hr
Pattern
A
A
HR1
HR2
2
3
4
5
6
24k
24k
12k
48k
48k
Gas pipe
Indoor
Unit
Liquid pipe
1) under 40m
2) Same horizontal level
Indoor
Indoor
Unit
Unit
Unit
Indoor
Indoor
Indoor
Indoor
Unit
Unit
Unit
Unit
HR1
HR2
1
2
3
36k
36k
36k
7
8
48k
12k
It's not allowed
Height
4
36k