n Select installation location of the HR unit suitable for following conditions
• Avoid a place where rain may enter since the HR unit is for indoor.
• Sufficient service space must be obtained.
• Refrigerant pipe must not exceed limited length.
• Avoid a place subject to a strong radiation heat from other heat source.
• Avoid a place where oil spattering, vapor spray or high frequency electric noise is expected.
• Install the unit at a place in which it is not affected by operation noise. (Installation within cell such as meeting
room etc. may disturb business due to noise.)
• Place where refrigerant piping, drain piping and electrical wiring works are easy.
481(18-10/11)
450(17-3/4)
174(6-7/8)
453(17-7/8)
No.
1
Low pressure Gas pipe connection port
2
High pressure Gas pipe connection port
3
Liquid pipe connection port
4
Indoor unit Gas pipe connection port
5
Indoor unit Liquid pipe connection port
6
Control box
7
Hanger metal
NOTICE
:
1. Be sure to install the inspection door at the control box side.
2. If reducers are used, servicing space must be increased equal to reducer's dimension.
All manuals and user guides at all-guides.com
Environment-friendly Alternative Refrigerant R410A
7
1
2
3
Inspection door(NOTICE 1)
(servicing space)
174(6-7/8)
Part Name
100mm(3-15/16 inch) more
100mm(3-15/16 inch) more
100mm(3-15/16 inch) more
300mm(11-7/8 inch) more
(NOTICE 2)
(Servicing space)
300mm(11-7/8 inch)more
(NOTICE 2)
(Servicing space)
124(4-7/8)
419(16-1/2)
6
61(2-7/16)
Description
PRHR030A/040A
Ø28.58(1-1/8) Brazing connection Ø22.2(7/8) Brazing connection
Ø22.2(7/8) Brazing connection
Ø12.7(1/2) Brazing connection
Ø15.88(5/8) Brazing connection
Ø9.52(3/8) Brazing connection
-
M10 or M8
100 more
100 more
(Serviceing space)
(Serviceing space)
(Serviceing space)
(Serviceing space)
(Serviceing space)
300mm(11-7/8 inch) more
(Servicing space)
100mm(3-15/16 inch) more
100 more
100mm(3-15/16 inch) more
100mm(3-15/16 inch) more
100 more
(Serviceing space)
(Serviceing space)
(Serviceing space)
(Serviceing space)
(Serviceing space)
450mm(17-3/4 inch) more
(Servicing space)
4
5
137(5-3/8)
(Unit: mm(inch))
PRHR020A
Ø19.05(3/4) Brazing connection
Ø9.52(3/8) Brazing connection
Ø15.88(5/8) Brazing connection
Ø9.52(3/8) Brazing connection
-
M10 or M8
Installation Manual 11