Verifying an abnormal state in the past although the abnormal state no longer occurs
1.
Set bit 1 of DIP switch SW803 to ON.
2.
Jot down the states of LED800 to LED804. (Display mode 1)
3.
Press SW800 for at least 1 second. The LED status changes to display mode 2.
4.
Find an error whose display mode 1 equals the LED states jotted down and display mode 2 equals the current
flashing states of LED800 to LED804 from the following table to identify the error.
• An outside air temperature (TO) sensor error can be checked only while it occurs.
No.
Cause
1
Normal
2
Discharge (TD) sensor error
3
Heat exchanger (TE) sensor error
4
Heat exchanger (TL) sensor error
5
Outside air temperature (TO) sensor error
6
Suction (TS) sensor error
7
Heat sink (TH) sensor error
Outdoor temperature sensor (TE/TS)
8
connection error
9
Outdoor EEPROM error
10
Compressor breakdown
11
Compressor lock
12
Current detection circuit error
13
Thermostat for compressor activated
Model data not set (on the service P.C.
14
board)
15
MCU-MCU communication error
16
Discharge temperature error
Abnormal power (open phase detected or
17
abnormal voltage)
18
Heat sink overheat
19
Gas leak detected
20
4-way valve reverse error
21
High pressure release operation
22
Outdoor fan motor error
23
Compressor driver short-circuit protection
Position detection circuit error in one-line
24
display
EN-95
Display mode 1
Display mode 2
D800
D801
D802
D803
D804
D800
D801
D802
(
:OFF
* The LEDs and DIP
switches are located
on the lower left of
the P.C. board of the
outdoor unit.
D803
D804
:ON
:Flashing)