Handling; Installation - S&P CACB-N Serie Manual De Instalación

Ocultar thumbs Ver también para CACB-N Serie:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Cabinet fan fixing
Ø11
L
Model
K
CACB-N 05
479
CACB-N 08
479
CACB-N 12
548
3.

INSTALLATION

3.1 Handling

3.2 Installation
The box must be attached to a flat support by the side holes provided for this purpose. It is recommended
to install it on vibration absorbers and connect it with flexible sleeves.
The CACB-N can be installed either for horizontal discharge or for vertical discharge by simply flipping the box.
Horizontal
discharge
Rejet Horizontal
K
M
Dimensions (mm)
L
M
N
350
98
175
400
98
250
450
110
300
Unpack the box.
To lift it, attach the box with 2 slings to the fixing straps located around
the discharge branch.
Vertical
discharge
The air tight installation of this box and its network should satisfy the
Rejet Vertical
technical conditions defined in DTU 68-3.
Important : Make sure that the motor's square cooling holes (located
under the electric connection box) are not obstructed.
P
N
Model
P
62
CACB-N 20
608
75
CACB-N 30
685
87
11/20
K
Ø11
Dimensions (mm)
K
L
M
450
130
675
59
NT_518736_CACB-N_ES-AN-FR-150528
N
P
300
105
400
82
Tabla de contenido
loading

Este manual también es adecuado para:

Cacb-n 05Cacb-n 08Cacb-n 12Cacb-n 20Cacb-n 30

Tabla de contenido