2.1. Rear panel view
1. RS-232 communication port
4. Share current port (depends on the model)
Stage Fan
|
9. Maintenance bypass switch
and 3 for details)
|
14. Output terminal: connect to mission-critical loads
non-critical loads
|
16. External battery terminal (depends on the model)
terminal
2.2. Setup the UPS
Installation and wiring must be performed in accordance with the local electric laws/regulations and execute the following
instructions by professional personnel.
Step 1. Make sure the mains wire and breakers in the building are enough for the rated capacity of UPS to avoid the hazard of
electric shock or fire.
Note: Do not use the wall receptacle as the input power source for the UPS, as its rated current is less than the UPS‟s
maximum input current. Otherwise the receptacle may be burned and destroyed.
Step 2. Switch off the mains switch in the building before installation.
Step 3. Turn off all the connected devices before connecting to the UPS.
Note 1: The cable for 15K/15KL should be able to withstand over 75A current. It is recommended to use 6AWG or thicker
wire for safety and efficiency.
Note 2: The cable for 20K/20KL should be able to withstand over 100A current. It is recommended to use 6AWG or
thicker wire for safety and efficiency.
Note 3: The selections for color of wires should be followed by the local electrical laws and regulations.
Segurança e harmonia
ININTERRUPTA
PH 9280 (15K) / PH 9290 (20K)
|
2. USB communication port
|
5. Parallel port (depends on the model)
|
10. Input circuit breaker
2. Installation and setup
Diagram 2: 15K/20K Input/Output Terminal
Diagram 3: 15K/20K Grounding Terminal
|
3. Emergency power off function connector (EPO connector)
| 6. Intelligent slot
|
13. Input/Output Terminal (refer to Diagram 2
|
15. Programmable output terminal: connect to
|
17. Utility input terminal
Uninterruptable Power Supply
EN
|
8. Power
|
18. Grounding
52
PH 9280 | PH 9290