ELECTRICAL INSTALLATION

!
WARNING
This Heater MUST be permanently Installed and hard
wired by an authorised/licenced person. Do Not perform
maintenance, or carry out installation or assembly
procedure while electrical power is switched on.
!
WARNING
ELECTRICAL SHOCK HAZARD! Serious injury or death may
occur. Disconnect from electrical supply before installing or
servicing this heater. Read and follow installation clearance
requirements outlined in this manual. The Appliance MUST
be connected to a properly grounded electrical source.
Disconnection incorporated in the fixed wiring is to be
provided
ELECTRICAL INSTALLATION
1. Check product label for correct voltage and wattage
- Make sure power source conforms to the heaters
requirements.
2. Junction box has a Ø22mm hole to suit M20 or
PG13.5 cord grip. Install cord grip with minimum rat-
ing of IPX4 to maintain the IPX4 rating of the heater.
Use cord grip suitable for at least 105°C.
3. For supply connection, use wires suitable for at least
105°C and at least 1.5mm2 for 2000W and 3000W
models, 2.5mm2 for 4000W and 6000W models. The
fixed wiring must be positioned away from & protect-
ed from the enclosure of the heater.
4. Make electrical connections in accordance with local
electrical code regulations. For outdoor installation
10
All manuals and user guides at all-guides.com
all connections must be made in accordance with local
electrical code regulations for outdoor wiring. Only
use wiring components approved for outdoor use with
minimum IPX4 rating. For all models the junction box has
one terminal block for the active and neutral connections
of the element. The polarity of power supply can be
connected to terminal block in either direction. Earth
ground wire screw is located in the end of junction box.
5. After installation, the distance between live parts and
earth (or earthed metal) should not be less than 2.5 mm.
The distance between live and neutral terminal should not
be less than 2.0 mm.
6. Assemble the junction box cover & gasket. Ensure that
the junction box cover gasket (supplied with unit) is
installed to maintain the IPX4 water ingress protection
rating of the heater. Failure to install correctly will void the
manufacturer's warranty.
2
1
www.bromicheating.com
ELECTRIC AL INSTALLATION
WIRING DIAGRAM
TUNGSTEN SMART-HEAT ELECTRIC
STANDARD INSTALLATION
2000W & 3000W MODELS
6
WIRING DIAGRAM
4
TUNGSTEN SMART-HEAT ELECTRIC
STANDARD INSTALLATION
4000W & 6000W MODELS
WIRING DIAGRAM
TUNGSTEN SMART-HEAT ELECTRIC
OPTIONAL INSTALLATION
4000W & 6000W MODELS
CONTINUED...
WARNING
Junction Box
240 V AC Single Phase
Heater must be permanently
installed and hard wired by an
authorised/licenced person.
Junction Box
WARNING
240 V AC Single Phase
Heater must be permanently
installed and hard wired by an
authorised/licenced person.
EARTH
WIRE
Junction Box
WARNING
240 V AC Single Phase
Heater must be permanently
installed and hard wired by an
authorised/licenced person.
www.bromicheating.com
www.bromicheating.com
EARTH
240 V AC
WIRE
SINGLE PHASE
AC
Heater Element 1
EARTH
240 V AC
WIRE
SINGLE PHASE
AC
Heater Element 1
Heater Element 2
240 V AC
240 V AC
SINGLE PHASE
SINGLE PHASE
AC
AC
Heater Element 1
Heater Element 2
11