Space heating
The ON/OFF signal and operation mode and temperature setting are set on the user interface. P_o(6) keeps running as long as the unit is
ON for space heating, SV1(4) keeps OFF.
Domestic water heating
The ON/OFF signal and target tank water temperature (T5S) are set on the user interface. P_o(6) stops running as long as the unit is ON
for domestic water heating, SV1(4) keeps ON.
AHS (auxiliary heat source) control
The AHS function is set on the indoor unit (See 9.2 "DIP switch settings overview")
1) When the AHS is set to be valid only for heating mode, AHS can be turned on in the following ways:
a. Turn on the AHS via BACKHEATER function on the user interface;
b. AHS will be turned on automatically if initial water temperature is too low or target water temperature is too high at low ambient
temperature.
P_o(6) keeps running as long as the AHS is ON, SV1(4) keeps OFF.
2) When the AHS is set to be valid for heating mode and DHW mode. In heating mode, AHS control is same as part 1); In DHW mode, AHS
will be turned on automatically when the initial domestic water temperature T5 is too low or the target domestic water temperature is too
high at low ambient temperature. P_o(6) stops running, SV1(4) keeps ON.
3) When the AHS is set to be valid, M1M2 can be set to be valid on the user interface. In heating mode, AHS will be turned on if MIM2 dry
contact closes. This function is invalid in DHW mode.
TBH (tank booster heater) control
The TBH function is set on the user interface. (See 9.2 "DIP switch settings overview" )
1) When the TBH is set to be valid, TBH can be turned on via TANKHEATER function on the user interface; In DHW mode, TBH will be
turned on automatically when the initial domestic water temperature T5 is too low or the target domestic water temperature is too high at
low ambient temperature.
2) When the TBH is set to be valid, M1M2 can be set to be valid on the user interface. TBH will be turned on if MIM2 dry contact closes.
Solar energy control
Hydraulic module recognizes solar energy signal by judging Tsolar or receiving SL1SL2 signal from user interface. The recognition method
can be set via SOLAR INPUT on the user interface. Please refer to 8.8.6/1 "For solar energy input signal" for wiring.(see 9.6.15 "INPUT
DEFINE")
1) When Tsolar is set to be valid, Solar energy turns ON when Tsolar is high enough, P_s(9) starts running; Solar energy turns OFF when
Tsolar is low, P_s(9) stops running.
2) When SL1SL2 control is set to be valid, Solar energy turns ON after receiving Solar kit signal from user interface, P_s(9) starts
running; Without solar kit signal. Solar energy turns OFF, P_s(9) stops running.
The highest outlet water temperature may reach 70°C, please beware of burns.
Make sure to fit the (SV1) 3-way valve correctly. For more details, please refer to 8.8.6 "Connection for other components.
At extremely low ambient temperature, the domestic hot water is exclusively heated by TBH, which assures
that heat pump can be used for space heating with full capacity.
Details on domestic hot water tank configuration for low outdoor temperatures (T4DHWMIN) can be found in
9.6.1 "DHW MODE SETTING".
CAUTION
NOTE
16