Notes)
1.
Field settings are normally applied to the entire remote control group, however if individual
indoor units in the remote control group require specifi c settings or for confi rmation that
settings have been established, utilize the mode number in parenthesis.
2.
Any features not supported by the connected indoor unit will not be displayed.
3.
When mode 10-2-01 is selected, only the return air temperature value is reported to the
multizone controller.
4.
The actual default deadband value will depend upon the indoor unit model.
7.

Test Operation

Also see installation manuals furnished with the indoor unit and the
outdoor unit.
Verify that the wiring of the indoor unit and the outdoor unit is completed.
Ensure that covers have been replaced on electrical component boxes for both indoor and outdoor
units prior to restoring power.
After refrigerant piping, drain piping and electric wiring are completed, clean inside of the indoor unit
and decorative panel.
Perform the test operation according to following procedure.
To protect the compressor, apply power to the outdoor unit at least 6 hours prior to test operation.
Set the remote controller display mode to standard or detailed display mode. Refer to Operation
Manual for the setting method.
Notes for backlight
● The backlight will be ON for 30 seconds by pressing any button.
The initial push of the button will only turn on the backlight. While the backlight is turned on,
the buttons assigned functionality will be available.
7-1
Set the operation mode to cooling by
using the remote controller.
7-2
Press and hold
Cancel button for
4 seconds or longer. Service settings
menu is displayed.
7-3
Select
Test Operation
settings menu, and press Menu/OK
button. Basic screen returns and Test
Operation is displayed at the button.
English
All manuals and user guides at all-guides.com
7-
1
7-
2
in the service
<Service settings menu screen>
7-
3
<Basic screen>
Cool
Set to
68
Press and hold Cancel
F
button for 4 seconds or
longer while the backlight
Return
Clean the filter
is on.
1/3
Service Settings
Test Operation
Maintenance Contact
Field Settings
Energy Saving Options
Prohibit Function
Min Setpoints Differential
Press Menu/OK button.
Setting
15