Connection of electrical consumers

The Pump-/PowerModule can op-
tionally switch an electrical con-
sumer. The wiring corresponds to the con-
nection of a pump. This electrical consumer
can either be controlled by all thermostats
(jumper to „P") or by individual thermostats
(jumper to 1-6). A second jumper allows
selecting the follow-up time: 0; 5; 10; 15
minutes.

Turn-on delay (PL 2000 Z2 / PL 4000 Z2 only)

Device with 2 minutes turn-on delay
The Pump-/PowerModule does not proc-
ess input pulses sent from the thermostat
with a duration of less than 2 minutes.
There is no output pulse, i.e. the poten-
tial-free contact of the relay will not be
switched. Input pulses longer than 2 min-
utes activate the Pump-/PowerModule.
The relay will be switched for 2 minutes.
This output pulse can be prolonged ac-
cording to the jumper position (green
jumper), see figure to the right.
��
Connection of more than one module
Input pulse < 2 min
Input pulse from
���
thermostat
no output pulse
from relay
PL 2000 / PL 4000
Input pulse ≥ 2 min
Input pulse from
thermostat
Relay output signal
�����
- Jmp 0 min
Jmp 5 min
�����
Jmp 10 min
������
Jmp 15 min
������
24 V