Electrical Wiring
(A) Definition and description of SW03
SW0 3_1
Address
setting mode
Code-set
SW03_2
indoor unit
~
address and
SW03_8
centralized
controller
address(Note2)
Note* :
• Set the address by code when connecting the centralized controller or gateway or charge system.
• Address of the centralized controller=communication address+0 or +64.
SW03_ 2=OFF, address of the centralized controller=communication address+0=communication
address
SW03_ 2=ON, address of the centralized controller=communication address+64 (applies
when the centralized controller is used and there are more than 64 indoor units).
• To use with 19848199886 use address setting as. Set SW03_1=0N and SW03_ 2=OFF; SW03_3,
SW03_ 4, SW03_5, SW03_6, SW03_7, and SW03_ 8 are address codes that are set according to
the actual address.
The address-setting function of the wired controller for ultrathin card machines is disabled.
(C) Jumper definition description
Electronic expansion valve PMV manual control settings(CN27, CN29)
Manually fully open CN27: short circuit CN27 for 2 seconds after power, the PMV fully opened.
Manually fully close CN29: short circuit CN29 for 2 seconds after power, the PMV fully closed.
26
C Lock function Activation:
o
Default : Deactivated
Activation: Press "Health" button on remote controller 8 times in 5 seconds, and when you hear the beep 4
times, the function is activated.
Deactivation: Press "Health" button on remote controller 8 times in 5 seconds, and when you hear the beep 2
times, the function is deactivated.
[1]
0
1
[2]
[3]
[4]
[5]
[6]
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
...
...
...
...
...
0
1
1
1
1
1
0
0
0
0
1
0
0
0
0
1
0
0
0
0
...
...
...
...
...
1
1
1
1
1
Address setting mode
Automatic setting (default)
Code-set address
[7]
[8]
Address of
indoor unit
0
0
0# (Default)
0
1
1#
1
0
2#
...
...
...
1
1
63#
0
0
0#
0
1
1#
1
0
2#
...
...
...
1
1
63#
20
Address of centralized
controller
0# (Default)
1#
2#
...
63#
64#
65#
66#
...
127#