Important Information For The Refrigerant; Installation Site - HTW ECO-THERMAL PLUS -V18WD2RN8PLUS Manual De Usuario E Instalacion

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

5 IMPORTANT INFORMATION FOR THE REFRIGERANT

This product has the fluorinated gas, it is forbidden to release to air.
Refrigerant type: R32; Volume of GWP: 675.
GWP=Global Warming Potential
Model
18kW
22kW
26kW
30kW
Frequency of Refrigerant Leakage Checks
- For unit that contains fluorinated greenhouse gases in quantities of 5 tonnes of CO
less than 50 tonnes of CO
at least every 24 months.
- For unit that contains fluorinated greenhouse gases in quantities of 50 tonnes of CO
less than 500 tonnes of CO
at least every 12 months.
- For unit that contains fluorinated greenhouse gases in quantities of 500 tonnes of CO
least every three months, or where a leakage detection system is installed,at least every six months.
- This air-conditioning unit is a hermetically sealed equipment that contains fluorinated greenhouse gases.
- Only certificated person is allowed to do installation, operation and maintenance.

6 INSTALLATION SITE

There is flammable refrigerant in the unit and it should be installed in a well-ventilated site. If the unit is installed
inside, an additional refrigerant detection device and ventilation equipment must be added in accordance with the
standard EN378. Be sure to adopt adequate measures to prevent the unit from being used as a shelter by small
animals.
Small animals making contact with electrical parts can cause malfunction, smoke or fire. Please instruct the custom-
er to keep the area around the unit clean.
Select an installation site where the following condition sare satisfied and one that meets with your customer's approval.
- Places that are well-ventilated.
- Places where the unit does not disturb next-door neighbors.
- Safe places which can bear the unit's weight and vibration and where the unit can be installed at an even level.
- Places where there is no possibility of flammable gas or product leak.
- The equipment is not intended for use in a potentially explosive atmosphere.
- Places where servicing space can be well ensured.
- Places where the units' piping and wiring lengths come within the allowable ranges.
- Places where water leaking from the unit cannot cause damage to the location (e.g. in case of a blocked drain pipe).
- Places where rain can be avoided as much as possible.
- Do not install the unit in places often used as a work space. In case of construction work (e.g. grinding etc.) where a lot of
dust is created, the unit must be covered.
- Do not place any object or equipment on top of the unit (top plate)
- Do not climb, sit or stand on top of the unit.
- Be sure that sufficient precautions are taken in case of refrigerant leakage according to relevant local laws and regulations.
- Don't install the unit near the sea or where there is corrosion gas.
When installing the unit in a place exposed to strong wind, pay special attention to the following.
Factory charged refrigerant volume in the unit
Refrigerant/kg
5.00
5.00
5.00
5.00
CAUTION
equivalent,at least every 12 months, or where a leakage detection system is installed,
2
equivalentat least every six months, or where a leakage detection system is installed,
2
WARNING
07
Tonnes CO
equivalent
2
3.38
3.38
3.38
3.38
equivalent or more,but of
2
equivalent or more, but of
2
equivalent or more,at
2