English
12.2
Parameter menu
Item
Duration of turbo
- Remaining fast run time up to automatic change to normal mode
Pause normal degaz
- Duration of pause between end of evacuation time and beginning of pump run
- Pause ON (beginning of night pause)
- Pause OFF (end of night pause)
Degassing
- Pump run time
- De-aeration time
System pressure
- pON: depending on the system type
- pOFF: depending on the system type
- Lower pressure limit (lower working pressure limit)
- Upper pressure limit (upper working pressure limit)
- Special system pressure (irrelevant for the operator)
Litres counter
- Litre/pulse: pulse water meter (can be set only by service personnel)
- Error litres counter: monitoring of delay of cycle of litres counter
Water treatment
Treatment capacity in case of integrated water softening module
Filling quantity:
Based on a continually referenced preceding
period of time (time window), the unit
allows using a certain number of filling
cycles that are separated by pauses from
one another. Cycles, pauses and time
windows (time spending) can be freely
parameterised.
32
Factory setting
10 hours
15 minutes
06:00 pm
08:00 am
Pressure dependent [s]
60 seconds
Tagus Vac 7: 1.5 bar
Tagus Vac 10: 1.5 bar
Tagus Vac 20: 3.0 bar
Tagus Vac 30: 5.0 bar
Tagus Vac 7: 2.0 bar
Tagus Vac 10: 2.0 bar
Tagus Vac 20: 4.0 bar
Tagus Vac 30: 6.0 bar
Depending on the system type
Depending on the system type
Factory setting
10 litre/pulse
40 minutes
100 litres
WILO 07/2018