PROPORTIONAL/MODULATING: 0(2)...10 VDC OR 10...0(2) VDC CONTROLLER OUTPUT
PROPORTIONAL ACTUATOR
DIP SWITCH POSITION
1
2
MODE
OFF
OFF
2-10V
OFF
ON
0-10V
ON
OFF
10-2V
ON
ON
10-0V
RED
BLACK
WHITE
+
1
2
3
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
2
24 VDC SUPPLY ACCEPTABLE.
Fig. 13. MVN713 with 0 (2)-10 VDC Control
VALVES WITH FAIL-SAFE ACTUATORS
1
24 VAC
2
1
LINE VOLTAGE POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
2
24 VDC SUPPLY ACCEPTABLE.
1
SPST
1
LINE VOLTAGE POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
Fig. 14. MS8105 with On/Off Control.
VRN DYNAMIC PRESSURE-REGULATING CONTROL VALVES AND ACTUATORS
2
24 VAC
+
–
0 (2)-10 VDC
CONTROLLER
M33140A
1
SPST
V
3
2
ACTUATOR
M34973
1
V
2
2
ACTUATOR
M34974
1
1
1
LINE VOLTAGE POWER SUPPLY.
PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
2
24 VDC SUPPLY ACCEPTABLE.
3
SET SWITCH TO FLOATING.
Fig. 15. MS7505 with Floating Control
1
0/2 TO 10 VDC
PROPORTIONING
CONTROLLER
–
+
FEEDBACK
1
LINE VOLTAGE POWER SUPPLY.
PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
2
24 VDC SUPPLY ACCEPTABLE.
3
SET SWITCH TO MODULATING.
Fig. 16. MS7505 with override to full open
1
0/2 TO 10 VDC
PROPORTIONING
CONTROLLER
FEEDBACK
1
LINE VOLTAGE POWER SUPPLY.
PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
2
24 VDC SUPPLY ACCEPTABLE.
3
SET SWITCH TO MODULATING.
Fig. 17. MS7505 with override to full closed
5
24 VAC
2
(Floating mode setting).
24 VAC
2
SPDT
(Modulating mode setting).
24 VAC
2
–
+
SPST
(Modulating mode setting).
ACTUATOR
1
V
2
3
OR +
OR N/A
4
5
FEEDBACK
2-10 VDC
10-2 VDC
0-10 VDC
3
10-0 VDC
Fltg, fwd
Fltg, rev
M34975
ACTUATOR
1
V
2
3
OR +
OR N/A
4
5
FEEDBACK
2-10 VDC
10-2 VDC
0-10 VDC
3
10-0 VDC
Fltg, fwd
Fltg, rev
M19576B
ACTUATOR
1
V
2
3
OR +
OR N/A
4
5
FEEDBACK
2-10 VDC
10-2 VDC
0-10 VDC
3
10-0 VDC
Fltg, fwd
Fltg, rev
M19577B
38-00005EFS—02