Add-on module for
Microstarter 4I / 4O
Operating Instructions
!
WARNING
HAZARDOUS VOLTAGE.
Can cause electrical shock
and burns.
Disconnect power before proceeding
with any work on this equipment.
Reliable functioning of the equipment is only ensured with certified components.
Applications
Installation / Wiring
AS-Interface
AUX PWR
Setting address
Screw
plug
Address
socket
Connecting
cable
The add-on module is designed for activating motor starters in motor terminal boxes (micro-
starters). The module has two 5-pin M12 sockets for connecting sensors (PNP) using two-wire
and three-wire technology.
The 16 pin socket connector (2 row) facing outwards on the back is for connecting a function
board (e.g. 3RK1902-0DB00).
The module is attached to the external wall of adap-
ted terminal box casings using four M3.5 x 20 mm
screws.
The communications connection and the auxiliary
power supply (AUX PWR) go through the yellow or
black AS-Interface trapezoidal-section cable.
To be able to set the address, you require the following:
• the addressing unit (order no. 3RK1904-2AB00) or the M236A diagnostics and service unit
(from GOSSEN Metrawatt).
Valid addresses are 1 to 31. Use each address once only.
After addressing has been completed, re-attach the screw plug to obtain degree of protection
IP 65
Screw plug: tightening torque 40 +/- 5 Ncm
Order No.: 3RK1702-2MB00-2AA0
3RK1902-0DA00
English
M12 pin assignments
Pin assignments:
5
1: +
4
1
2: IN (jumpered)
–
3:
3
2
4: IN (jumpered)
5: not used
Pin assignments for 16 pin socket connector
1 DC 24 V +
2 DC 24 V +
red
1
2
3 DO 2 (brake)
4 DO 3 (reset)
4
3
5 DO 1 (counter-
clockwise rotation)
6
5
6 Sensor 2 (back)
7 DC 15 V +
8
7
8 Sensor 2 (+)
9 not used
10
9
10 DO 0 (clockwise
rotation)
12
11
11 Sensor 1 (back)
12 Sensor 1 (+)
13
14
13 DI 1 (RUN)
14 DI 0 (FAULT)
16
15
15 DC 24 V –
16 DC 24 V –
3