the voltage between the live wires (L1-L2, L2-L3, L3-L1 ➜
Fig. 12C) does not exceed 230 V.
In case of error (ground fault), the voltage between the live wire
and PE must not exceed 230 V.
ƒ
During external connection of the pump deactivate a pulse of
the voltage (for example phase angle control).
ƒ
Switching the pump via triacs/solid-state relays must be ex-
amined on a case-by-case basis.
ƒ
During deactivation with on-site power relay: Rated current
≥ 10 A, rated voltage 250 V AC
ƒ
Observe the switching frequency:
– Switch-on/off procedures via mains voltage ≤ 100/24 h
– ≤ 20/h for a switching frequency of 1 min. between switching
on/off via mains voltage
ƒ
If a residual-current device (RCD) is used, it is recommended to
use an RCD type A (pulse current sensitive). Check that the rules
for the coordination of electrical equipment in the electrical in-
stallation are observed and, if necessary, adjust the RCD accord-
ingly.
ƒ
Observe leakage current I
eff
ƒ
The electrical connection must be made via a fixed connecting
cable equipped with a connector device or an all-pole switch
with a contact opening width of at least 3 mm (VDE 0700/
Part 1).
ƒ
To protect against leakage and for strain relief to the threaded
cable gland, use a connecting cable with sufficient outer dia-
meter ➜ Fig. 15.
ƒ
Use a heat-resistant connecting cable for fluid temperatures ex-
ceeding 90 °C.
Installation and operating instructions Wilo-Yonos MAXO /-D/-Z
≤ 3.5 mA for each pump.
ƒ
Lay the connecting cable in such a way that it does not make
contact with the pipes or the pump.
6.3
Connection options
➜ Fig. 12
NOTICE
3~ 400 V without neutral conductor N: Upstream
mains transformer.
6.4
Twin-head pumps
Only operate as main and standby pump with automatic fault-actu-
ated switchover:
1. Individually connect and secure both motors.
2. Provide separate switchgear.
3. Make the identical settings.
6.5
Collective fault signal (SSM)
The contact of the collective fault signal (potential-free normally
closed contact) can be connected to a building automation system.
Internal contact is closed in the following cases:
ƒ
The pump has zero current.
ƒ
There is no fault.
ƒ
The control module has failed.