6. Commissioning, operation
6. Commissioning, operation
CAUTION!
Prior to commissioning, the pressure sensor must be subjected to a visual inspection.
EN
Leaking fluid is indicative of damage.
■
Only use the pressure sensor if it is in perfect condition with respect to safety.
■
CAUTION!
The model O-10 (T) pressure sensor must not be exposed to any condensation.
6.1 Mechanical mounting
Required tool: Open-ended spanner (spanner width 24)
The sealing faces at the instrument have to be undamaged and clean.
■
When screwing the instrument in, the force required to do this must not be
■
applied through the casing, but only through the spanner flats provided for
this purpose and using a suitable tool.
When screwing in, do not cross the threads.
■
For information on tapped holes and welding sockets, see Technical
■
information IN 00.14 at www.wika.com.
22
WIKA operating instructions pressure sensor, model O-10
Spanner flats