en - Original instructions
Quick Menus
Q1 My Personal Menu
Q2 Quick Setup
Q3 Function Setups
Q4 Start-Up Genie
3.2 Start-Up Genie (Smart Setup)
Power on the drive(s) and follow the steps below to program the drive.
Regional Settings
International
Language
English
Selection Pump
Application Type
Booster
Motor Power
3 kW
Motor Nominal Voltage
400 V
Motor Frequency
50 Hz
Motor Nominal Speed
2885 RPM
Motor Current
9 A
Current Limit
110%
Motor Type
Surface
Sleep Speed/Low Limit
20.0 Hz
Filter Type
None
12
To navigate the Start-up Genie
menu:
• Use OK button to select the
menu item;
• Once selected, use the UP
and DOWN arrow buttons to
change the value;
• Confirm with OK button;
• Use DOWN button to go to
next menu item.
1. Select International in Regional
Settings.
2. Select the Language and pro-
ceed with the down arrow.
3. Select pump application type
based on your system: Booster or
HVAC.
4. Enter the rated motor power in
kW from the motor data plate for
the following motor data.
4a. Set the rated motor voltage.
4b. Select Motor Frequency.
4c. Enter Motor Nominal Speed.
4d. Enter the rated motor current.
4e. Set the Current Limit equal to
(Service Factor Amps/Full Load
Amps).
• For example, if the Motor Cur-
rent (FLA) indicated on the
motor nameplate is 5.6A and
the Motor Service Factor Cur-
rent (SFA) is 6.4A, enter 114%
for Current Limit (%). Be sure
to properly set the Motor Cur-
rent (FLA) and Current Limit.
4f. Select Submersible for bore-
hole application or Surface for
above ground motors.
4g. Enter the minimum limit for
motor speed. The motor speed
low limit can be set to correspond
to the minimum output frequency
of the motor shaft.
4h. Select correct filter type if you
have installed a filter between
drive and motor. Refer to the full
manual for details.
Automatic Motor
Adaption (AMA)
Enable Complete AMA
Continue to the

application setup?

Yes
3.3 Application Setup

3.3.1 Select Operating Mode

Select operating mode based on your system.
Operating Mode
CHANGING OPERATING
MODE WILL OVERWRITE
CURRENT SETUP
Single Pump Control
Operating Mode
CHANGING OPERATING
MODE WILL OVERWRITE
CURRENT SETUP
Multipump Control
Operating Mode
CHANGING OPERATING
MODE WILL OVERWRITE
CURRENT SETUP
Speed Control
3.3.2 Single Pump Control
Example for Constant pressure, low power rate pump.
Application Type
Constant Pressure
Pressure Control Units
bar
Ramp Time
Fast
Regulation Band
20%
Would you like to Autoset
the rest of the settings?
Yes
Setpoint
3,5 bar
Constant Pressure
Default Values Loaded
(See IOM)
[OK]
Start-Up Genie Complete
Press [OK] to Exit
3.3.3 Multi-pump Multicontrol
This example is for four pumps, constant pressure control.
Starting from the first inverter to the last, configure each inverter with
same parameters values.
Lowara Aquavar
4i. Perform AMA (Automatic Motor
Adaption) to detect motor parame-
ters for better efficiency and motor
control.
5. Select Yes to continue with Ap-
plication Setup.
1. Single Pump Control (continue
to
Single Pump Control
on page
12.
2. Multi-pump Control (continue to
Multi-pump Multicontrol
on page
12)
3. Speed Control for fixed speed
application (continue to
Speed Con-
on page 13)
trol
1. Selectable applications are
Constant Pressure, Flow Control
and Level Control. Refer to the full
manual for details.
2. Select Pressure Control Unit.
3. Select Ramp Time. See
Ramp
Control description
on page 14 for
details.
4. Set desired pressure regulation
band for Double Ramp Control
Logic. See
Ramp Control descrip-
tion
on page 14 for details.
5. Select Yes to Autoset the rest
of the settings. See
Autoset Param-
eters Extract
on page 15 for de-
tails.
6. Set desired setpoint.
7. Default Value Loaded. Press
OK to continue.
8. Programming Completed. Se-
lect OK to Exit from Start-up Gen-
ie.
®
QUICK START GUIDE