FRONT PANEL INDICATORS (Continued)
3) Red "PUSH" To Activate / Alarm When Lit" LED
(sounder matches pulse rate).
a. Pulsing 1 x 1 sec. indicates Pre-Alarm Condition, Alarm
Only Programming or Isolate Mode.
b. Pulsing 2 x 1 sec. indicates Alarm Condition and TD1
(time delay #1) starts countdown (last 5 sec. pulsing
increases to 4 x 1 sec.).
c. Pulsing 4 x 1 sec. indicates last 5 sec. of TD1 and TD2
(time delay #2) continues with pulsing at 4 x 1 sec. until
end of countdown.
d. Steady-on for 10 sec. indicates Release Activated.
e. LED is also a button, see page 2 for manual activation of
fire suppression system.
4) DELAY/Reset/Silence Button
a. Icons on button represent options for system control.
During Time Delay, press button to restart Time
Delay.
When sounder is pulsing, press button to silence.
Press and hold button for 3 sec. to reset system.
PAGE 6