Installation
Turn the unit on. From the SRCOOLNET2 user interface, make sure that the
ENVIROSENSE has been discovered/discover it. Click the 'Remote' checkbox to
override the setpoint control on the device display panel
setpoint you wish to target and press ENTER. The setpoint control on the device
display panel will be overridden.
B
The SRCOOL7KRM or SRCOOL18K will now begin cooling when the temperature
reading at ENVIROSENSE equals or exceeds the setpoint value you entered.
When the temperature falls below this setpoint, the unit will stop cooling. If the
'Always On' checkbox is checked, the fans will remain running when the unit
stops cooling. If the 'Always On' checkbox is unchecked, the fans will shut off
and the SRCOOL7KRM or SRCOOL18K display will extinguish. Once the
temperature reaches the setpoint again, the unit will restart and begin cooling
until the temperature reported by ENVIROSENSE returns below the setpoint. This
cycle will continue indefinitely until you select STOP from the SRCOOLNET2 user
interface or turning the SRCOOL unit off via the device display panel.
15-02-247-93342E.indb 11
B
11
. Type in the remote
4/9/2015 9:52:09 AM