GB
Check that the unit is connected to the correct mains power supply voltage, and that
it is protected by the correct fuse size. A protective earth connection must be made,
in accordance with regulations.
Recommended fuse sizes and minimum cable areas
50Hz
Mains voltage
Primary current
60% duty cycle
100% duty cycle
Mains cable area (4x)
Fuse anti--surge
60Hz
Mains voltage
Primary current
60% duty cycle
100% duty cycle
Mains cable area (4x)
Fuse anti--surge
* AAG (Arc Air Gouging)
NB: The mains cable areas and fuse sizes as shown above are in accordance with Swedish
regulations. They may not be applicable in other countries: make sure that the cable area and fuse
sizes comply with the relevant national regulations.
mxx02cwe
Rating plate with supply connection data
Mig 4002c
230/400--415/500 V
56/32(43*)/26 A
43/25/20 A
2
10/4/4 mm
35/25(50*)/20 A
Mig 4002c
230/440--460 V
56/32(43*)/26 A
43/25/20 A
2
10/4/4 mm
35/25(50*)/20 A
- - 10 - -
Mig 5002c
230/400--415/500 V
75/43(50*)/34 A
57/33/26 A
2
16/6/6 mm
63/35(50*)/35 A
Mig 5002c
230/440--460 V
75/43(50*)/34 A
57/33/26 A
2
16/6/6 mm
63/35(50*)/35 A
Mig 6502c
230/400--415/500 V
103/59(65*)/47
80/46/37 A
2
25/10/10 mm
80/50(63*)/50 A
Mig 6502c
230/440--460 V
103/59(65*)/47
80/46/37 A
2
25/10/10 mm
80/50(63*)/50 A