• DRY CONTACT C3-C3
CONFIGURATION
IMPORTANT!: The function is available by
connecting the dry contact C3-C3 on the power
board and is active only if JUMPER MC4 is open.
The dry input contact (NC
types of operation that can be activated by means
of the on-board display:
• Fireplace "FirE" function (default)
• Boiler "bOIL" function
From the main menu, access the "TECH" menu
and press the "+" key to display the "C3C3" menu.
Then press "Enter" to confirm.
Using the "+" key, choose either the FirE or
bOIL function.
Confirm the selected function with the "Enter" key.
C3C3
ENTER
NO*= normally open contact
NC*= normally closed contact
*
) C3-C3 enables two
FirE
ENTER
boIL
ENTER
• DRY CONTACT FC-FC
CONFIGURATION
IMPORTANT!: The function is available by
connecting contact FC-FC on the power board.
Contact FC-FC (230V output) enables two types
of operation that can be activated from the on-
board display:
• "ALrN" function (default)
Remote alarm status signal
• "ConS" function 230V enabling signal for
synchronisation with external units.
From the main menu, access the "TECH" menu
and press the "+" key to display the "FCFC" menu.
Then press "Enter" to confirm.
Using the "+" key, choose either the ALrN or
ConS function.
Confirm the selected function with the "Enter" key.
FcFc
ENTER
ATTENTION!: in case of units supplied
without T-EP you are recommended to
activate the remote alarm that signals
the filters replacement
English
AlrN
ENTER
COnS
ENTER