For other connection, the phase shift to be programmed can be selected from the tables
in the appendix A6.
Please note that the RVT can adapt automatically the phase shift during automatic
commissioning.
4.3.1.3 User settings
Start screen-> Settings-> Manual settings-> user settings
User Settings allows the users to set different target power factors and alarm delays.
Figure 37: RVT user settings
Target cos j: target displacement power factor.
The target cos j value can be set between 0.70 inductive and 0.70 capacitive.
indicates an inductive cos j and
indicates a capacitive cos j.
Night cos j: alternative displacement power factor (disabled by default).
Switching from the target cos j to the target night cos j is performed with an external
signal applied on the external digital input IN 1 +/- (description in paragraph 2.4).
Figure 38: RVT user settings: enable night and reg. power factor
Reg. cos j: alternative target displacement power factor. Activated when power flow is
reversed: P < 0 (disabled by default).
46 Measurements and Settings ç Power Factor Controller RVT