Centralita de relés de protección diferencial
Ocultar thumbs Ver también para CBS-4:

Enlaces rápidos

Código
code
CBS - 4
P12711
REC
.
DESCRIPCIÓN GENERAL
- Dispositivo con 4 relés diferenciales independientes y programables.
4 canales de disparo.
- Dispone de 5 salidas. 4 para disparo por relé y la de señalización por prealarma.
- Dispone de 1 entrada para realizar un Disparo/Rearme externo.
- Montaje en Carril DIN 46277 (EN 50022) o panel 72x72 mediante accesorio (M5ZZF1)
- Asociado a transformador de corriente diferencial externo serie WG/WGS.
- Comprueba conexión con transformador exterior WG/WGS mediante test inductivo.
- La detección y medida de la fuga se realiza calculando su verdadero valor eficaz (TRMS).
- Visualización por display de los valores de ajuste y de la corriente diferencial
instantánea
CONSIDERACIONES INICIALES
COMPROBACIONES A LA RECEPCIÓN
Asegurarse del cumplimiento de:
- El equipo corresponde a las especificaciones de su pedido.
- El equipo no ha sufrido desperfectos durante el transporte.
Para más información, puede descargarla de nuestra web, www.circutor.es
PRECAUCIONES DE SEGURIDAD
Para la utilización segura del equipo, es fundamental que las personas que lo instalen o
manipulen, sigan las medidas de seguridad habituales, así como las advertencias en dicha
guía rápida.
El CBS-4 es un equipo diseñado específicamente para ser instalado dentro de un cuadro
eléctrico o envolvente, con fijación en carril DIN o en panel mediante accesorio. Dispone
de led luminoso (ON) indicando que hay presencia de tensión. Aunque este led no esté
encendido, no exime al usuario de comprobar que el equipo está desconectado de toda de
toda fuente de alimentación.
A su vez, el circuito de alimentación debe estar provisto de un interruptor magnetotérmico o
dispositivo equivalente para desconectar el equipo de la red de alimentación.
INSTALACIÓN Y PUESTA EN MARCHA
La presente guía rápida contiene informaciones y advertencias que el usuario tiene que
respetar para garantizar el funcionamiento seguro del equipo. En su funcionamiento
habitual no debe ser utilizado hasta su instalación definitiva en el cuadro eléctrico.
!
Si se utiliza el equipo de forma no especificada por el fabricante, la protección
puede resultar comprometida.
Cuando sea probable que el equipo haya perdido la protección de seguridad (presencia de
daños visibles) debe desconectarse la alimentación del equipo. En este caso póngase enc
contacto con el servicio técnico cualificado, o bien, con nuestro S.A.T. (Servicio Asistencia
Técnica).
INSTALACIÓN DEL EQUIPO
La instalación en carril DIN. Por el toroidal asociado tienen que pasar todos los conductores
activos que alimentan a las cargas o parte de la instalación en la que se requiera realizar la
protección diferencial con este equipo. En instalación monofásica (fase y neutro, L y N),
trifásica (las tres fases, L1,L2 yL3) o trifásica mas neutro (L1, L2, L3 y N). En el interior del
cuadro eléctrico. A tener en cuenta, que con el equipo conectado, los bornes y la apertura
de cubiertas o eliminación de elementos, puede dar acceso a partes peligrosas al tacto.
El equipo no debe ser utilizado hasta que haya finalizado por
completo su instalación. El equipo debe conectarse a un circuito
de alimentación protegido con fusibles acorde con el rango de
alimentación y consumo del mismo. A su vez el circuito de
alimentación tiene que estar provisto de un interruptor
magnetotermico o dispositivo equivalente para desconectar el
equipo de la red de alimentación. Durante el conexionado se
aconseja una sección cable permitida entre 1- 1.5 mm . Un par
de apriete recomendado de 0,5-0,6 N.m y una longitud a
desaislar cable de 7 mm.
CONTACTO DISPARO/TRIPPING CONTACTS
Salida Relé Canal T1
13 14
Output Relay Channel T1
Salida Relé Canal T2
14 15
Output Relay Channel T2
Salida relé canal T3
7
8
Output relay channel T3
Salida relé canal T4
9
8
Output relay channel T4
1 11
Salida Pre-alarma / Pre-alarm output
M98203801-20-16A
Centralita de relés de protección diferencial CBS- 4
Multipoint earth leakage relay CBS- 4
Tipo
Sensibilidad (A)
Type
Sensivity
0,03-0,1-0,3-0,5-1-3
por ajuste directo
CBS-4
by direct setting
5-10-30 por/by SETUP
¡ IMPORTANTE !
2
Peso / Wheight : 168 gr
MARCADO DE BORNES / TERMINAL CONNECTIONS DESIGNATIONS
TRANSFORMADOR DIFERENCIAL
CORE BALANCE
2
Entrada 1S2 común/Common input 1S2
3
Entrada 1S1-T4 / Input 1S1-T4
4
Entrada 1S1-T3 / Input 1S1-T3
5
Entrada 1S1-T2 / Input 1S1-T2
6
Entrada 1S1-T1 / Input 1S1-T1
Retardo disparo (s)
Tripping delay
INS-SEL-0,02-0,1-0,2-0,3-0,4-0,5-0,75-1
por ajuste directo / by direct setting
3-5-10 por/by SETUP
Por ejemplo CBS-4 alimentado a 110 V c.a /
GENERAL DESCRIPTION
-
Device with 4 independent and programmable differential relays. 4 tripping channels.
- It has 5 outputs. 4 trip relays and prealarm signal relay.
- It has one input for external Trip/Reclose.
- Mounting in DIN rail 46277 (EN 50022) or PANEL 72x72 by means accesories M5ZZF1.
- Associated to a WG/WGS Series external, toroidal current transformer.
- It verifies connection with external transformer WG/WGS by inductive tests.
- Leakage detection and measurement is via calculating its true effective value (TRMS).
- Displays setting values and instant current different to its associated units
PRELIMINARY CONSIDERATIONS
CHECKS ON RECEPTION
On receving the instrument, check the following points:
- The unit specifications are the same as those on your order.
.
- Check that the device has not suffered any damage during transport.
You can download more information from CIRCUTOR website, www.circutor.es
SAFETY PRECAUTIONS
The staff using or handling the unit must follow the common safety measures and warnings
included in the instruction manual.
The CBS-4 unit has been specifically designed for its installation in a electric board,
enclosure to a DIN rail or mounted in panel by means of accesories. It has a flashing green
led (ON) when it is operating and, therefore, it shows that there is voltage and current in the
electronic circuit. The user must make sure that the equipment is not conected to the power
supply at all the times, even when the LED is not flashing
Likewise, the power supply circuit must have a built-in cicuit breaker or equivalent device to
disconnect the unit from the power.supply network.
INSTALLATION AND START-UP
The user must take into account and observe the informations and warnings included in this
instruction manual to guarantee the correct operation of the equipment and comply whit the
safety specifications. The equipment must not turned on until is fully installed in the
electrical panel.
!
The unit´s protections systems might not be effective if the unit is used for purpose
other than those specifications by the manufacturer.
Disconnect the equipment from the power supply when the unit´ssafety protection systems
are not working or there are signs of a problem (in case of visible damage). In this case,
contact a qualified technical service or with our own technical service (TAS).
INSTALLING THE EQUIPMENT
DIN rail installation. Through the CBT must pass all live conductors supplyng electrical
energy to loads or part of the installation which requires it to earth leakage protection with
this device. In single-phase installation (phase and neutral, L and N), three phase - 3 wires
(three phases, L1, L2 and L3) or three phases - 4 wires (L1, L2, L3 and N). All connections
Should be inside t he electrical board. Please note that with the connected equipment,
67,9
52,5
43,5
cotas en mm
dimensions in mm.
ENT. DISPARO/REARME EXTERNA
EXTERNAL TRIP / RECLOSE
10 12
Entrada tensión / Input voltage
ALIMENTACIÓN/POWER SUPPLY
10
Alimentación / Supply (A1)
11
Alimentación / Supply (A2)
P 1 X X X X 0 0 X
Comunicaciones
Communications
Código
Code
Tensión de
No disponible
alimentación
Not available
Power supply
For instance CBS-4
supplied by
110 V a.c..
¡ IMPORTANT !
terminals and opening covers or removing elements, can
give access to dangerous parts to touch. The equipment
must not be used until it has completely finished installation.
The unit must be connected to a power supply circuit
protected by fuses in line with the range and power
consumption. In turn, the supply circuit must be provided
with a circuit breaker or equivalent device to disconnect the
equipment from the mains. During the wiring cable is
advisable a section permitted between 1 - 1.5 mm2. A
recommended torque of 0.5-0.6 N.M. Cable Stripping Tools
length 7 mm.
Fijación carril/
Fixed by rail DIN 46277
(EN 50022)
10
11
12
Reset
CBS-4
Test
1
2 3
4 5 6
Código interno
Internal code
0
230 V a.c.
110 V a.c.
1
24 / 48 V c.a./a.c.
4
24/125 V c.c./d.c.
P12711001
.
.
13
14
15
8
9
7
Pag. 1/4
loading

Resumen de contenidos para Circutor CBS-4

  • Página 1 The CBS-4 unit has been specifically designed for its installation in a electric board, enclosure to a DIN rail or mounted in panel by means of accesories. It has a flashing green El CBS-4 es un equipo diseñado específicamente para ser instalado dentro de un cuadro led (ON) when it is operating and, therefore, it shows that there is voltage and current in the eléctrico o envolvente, con fijación en carril DIN o en panel mediante accesorio.
  • Página 2 Centralita de relés de protección diferencial CBS- 4 Multipoint earth leakage relay CBS- 4 DESCRIPCIÓN DE LOS LED Y PULSADORES DESCRIPTION LED AND BUTTONS - Indicación del estado del equipo mediante display y 2 LED. Shows equipment status via a display and 2 LED's. - Ajuste y programación del equipo mediante 5 pulsadores.
  • Página 3 NORMATIVA STANDARD Cumple con la Normativa IEC62020 , IEC 60947-2 Anexo M. Meet with standard IEC62020, IEC 60947-2 Annex M. ESQUEMAS DE CONEXIÓN / CONNECTION DIAGRAM CBS-4 + WG/WGS ALIMENTACIÓN / SUPPLY Supply Supply L1 L2 L3 ON / OFF externo...
  • Página 4 Tel: (+34) 93 745 29 19 (Fuera de España) Fax: (+34) 93 742 29 14 Fax: (+34) 93 745 29 14 Vial Sant Jordi s/n Vial Sant Jordi s/n email: [email protected] email: [email protected] 08232 Viladecavalls (Bacelona) SPAIN 08232 Viladecavalls (Bacelona) SPAIN www.circutor.com www.circutor.es...