REMEMBER
• Our mixers must be installed by professional installers in accordance with current regulations
and recommendations in your country, and the specifications of the fluid engineer.
• Sizing the pipes correctly will avoid problems of flow rate, pressure loss and water hammer (see
calculation table in our brochure and online at www.delabie.com).
• Protect the installation with filters, water hammer absorbers and pressure reducers to reduce the
frequency of maintenance (recommended pressure from 1 to 5 bar maximum).
• Install stopcocks close to the mixer to facilitate maintenance.
• The pipework, filters, non-return valves, stopcocks, bib taps, cartridge and all sanitary fittings should
be checked at least once a year, and more frequently if necessary.

TEMPERATURE SETTING

Our mixers are pre-set in factory at 3 bar (300 kPa) with equal hot and cold water pressures and a hot
water pressure of 65°C ±5°C and cold water 15°C ±5°C.
If the conditions of use are different, the mixed water temperature can differ from the temperature pre-set
in factory. You should reposition the control at the corresponding temperature (fig. D, E and F).
CHEMICAL AND THERMAL SHOCKS
• This product has been designed to withstand both thermal and chemical shocks in line with current
regulations.
• Thermal shocks can be carried out at the hot water system temperature without removing the control:
- Press the red button using a pointy object Ø 4mm max.
The temperature limiter at 41°C will unblock.
- ½ turn anti-clockwise in order to achieve the maximum temperature supplied by the network.
• The cold water can now be cut without it cutting off the hot water.
• Once the thermal shock has been carried out, do not forget to return to the starting
position by turning the control clockwise until the red button clicks (in order to respect
the safety of the hot water limiter).
• Thermal shocks can be carried out at the hot water system temperature without removing the control:
- Press the red button using a pointy object Ø 4mm max.
The temperature limiter at 41°C will unblock.
- ½ turn anti-clockwise in order to achieve the maximum temperature supplied by the network.
• The cold water can now be cut without it cutting off the hot water.
• Once the thermal shock has been carried out, do not forget to return to the starting
position by turning the control clockwise until the red button clicks (in order to respect
the safety of the hot water limiter).