ENG
3.7.2
Electrical data
Designation
Rated voltage * ***
Rated frequency *
Functional area
Power consumption * A35 / A35
Condensate evaporator power consumption
Nominal current *
Start-up current *
*
Data on the type plate.
***
Adapt the upstream fuse if the rated voltage changes, see "Adapting the unit to the mains voltage", Page 49.
3.7.3
Dimensions
Designation
Height
Width
Depth with cover (standard)
Weight
Installation attitude
Unit construction
3.7.4
Other unit data
Designation
Anti-corrosion protection
Protection category
Operating Manual | Roof-mounted Cooling Unit | Multi Controller (MC) – 115 V | 086100029c
P
el
P
30 to 110 W (A35/A35 approx. 70 W)
el
I
nom max
I
Start max
Standard: Steel sheet/plastic
Standard: Galvanized, electrostatically powder-coated
(200°C)
Variant: Stainless-steel hood
When used as intended:
•
IP 54 relative to the switch cabinet (EN 60529).
•
IP 34 relative to the environment (EN 60529).
Model DTT 6301
115 V, 1~
60 Hz
DIN IEC 60038
1894 W
20 A
34 A
Model DTT 6301
435 mm
595 mm
495 mm
44 kg
Vertical
28/29