ENG
3.7.2
Electrical data
Designation
Rated voltage * ***
Rated frequency *
Functional area
Power consumption * A35 / A35
Condensate evaporator power consumption
Nominal current *
Start-up current *
*
Data on the type plate.
***
Adapt the upstream fuse if the rated voltage changes, see "Adapting the unit to the mains voltage", Page 50.
3.7.3
Dimensions
Designation
Height
Width
Depth with cover (standard)
Weight
Installation attitude
Unit construction
3.7.4
Other unit data
Designation
Anti-corrosion protection
Protection category
Operating Manual | Roof-mounted Cooling Unit | Multi Controller (MC) – 230 V | 086100021d
P
50 Hz
el
P
60 Hz
el
P
el
I
50 Hz
nom max
I
60 Hz
nom max
I
50 Hz
Start max
I
60 Hz
Start max
Standard: Galvanized, electrostatically powder-coated
(200°C)
Variant: Stainless-steel hood
When used as intended:
•
IP 54 relative to the switch cabinet (EN 60529).
•
IP 34 relative to the environment (EN 60529).
Model DTT 6401
230 V, 1~
50/60 Hz
DIN IEC 60038
1000 W
1265 W
30 to 110 W (A35/A35 approx. 70 W)
4.5 A
5.7 A
20 A
21 A
Model DTT 6301
435 mm
595 mm
495 mm
46 kg
Vertical
Standard: Steel sheet/plastic
28/29