3.7

Technical data

3.7.1

Refrigeration circuit

Designation
Cooling capacity at A35 / A35 */*
Cooling capacity at A50 / A35 */*
Refrigerant type *
Refrigerant quantity *
Temperature setpoint (factory setting)
Fault indication: Switch cabinet interior
temperature
(factory setting)
Ambient air temperature
Switch cabinet interior temperature
Air volume flow, exterior circuit
Air volume flow, interior circuit
Condensate separation
Sound pressure level (1 m)
Tab. 6: Refrigeration data
*
Data on the type plate.
NOTE
The use of optional filter mats reduces the cooling capacity
3.7.2

Electrical data

Designation
Rated voltage * ***
Rated frequency *
Functional area
Power consumption * A35 / A35
Condensate evaporator power consumption
Nominal current *
Start-up current *
*
Data on the type plate.
***
Adapt the upstream fuse if the rated voltage changes, see "Adapting the unit to the mains voltage", Page 51.
Operating Manual | Roof-mounted Cooling Unit | Multi Controller (MC) – 400 V, 2~ | 086100031c
Q
50 Hz
0
Q
60 Hz
0
Q
50 Hz
0
Q
60 Hz
0
P
50 Hz
el
P
60 Hz
el
P
el
I
50 Hz
nom max
I
60 Hz
nom max
I
50 Hz
Start max
I
60 Hz
Start max
Model DTT 6201
1000 W
1100 W
600 W
640 W
R134A
400 g
+35 °C (+95 °F)
SC-Controller: > +50 °C (+122 °F)
MC-Controller: > +52 °C (+125.6 °F)
+15 °C (+59 °F) to +55 °C (+131 °F)
+25 °C (+77 °F) to +45 °C (+113 °F)
1820 m³/h
570 m³/h
Condensate evaporator
≤ 62 dB(A)
Model DTT 6201
400 V, 2~
50/60 Hz
DIN IEC 60038
530 W
660 W
30 to 110 W (A35/A35 approx. 70 W)
1.6 A
1.7 A
5.2 A
6.2 A
27/80