Code
Function
Static Pressure
32
step
33
Guard timer
34
Set point range Lock
Cooling thermal off
35
Fan operation
Use Primary Heater
36
control
37
Hold Enable / Disable
Air conditioner Fan
38
operation interlocked
with ventilation
Indoor unit
39
Auto-Start setting
Occupy sensor 'occupy
40
maintain' time setting
h Some contents may not be displayed depending on the product function.
00: use static pressure (code 06) set value
01~11: static pressure step (code 32) set value
00: 0 minute
01: 15 minutes
02: 30 minutes
03: 45 minutes
04: 60 minutes
01: Cooling
- Upper limit / Lower limit
(50~99 °F / 10~37.5 °C)
02: Heating
- Upper limit / Lower limit
(40~90 °F / 4~32 °C)
00: Cooling thermal off Fan speed -Low
01: Cooling thermal off Fan OFF
02: Cooling thermal off Fan speed setting value
00: Cancel primary heater control
01: use primary heater control
00: Hold Function disable
01: Hold Function enable
00: air-conditioner fan operate very low
01: air-conditioner fan off
00: Use indoor unit auto restart
01: not use indoor unit auto restart
00: 0 minute
01: 10 minutes
02: 30 minutes
03: 60 minutes
INSTALLATION INSTRUCTIONS
Value
65